BLUEHELIX TECH RRT 24 H
ON/OFF (A fig. 21) configuration
Table 3- Switch A setting
DHW configuration
Parameter b06
b06=0
b06=1
b06=2
b01 = 1 o 3
b06=3
b06=4
b06=0
b06=1
b01 = 2 o 4
b06=2
b06=3
b06=4

2.6 Fume ducts

THE BOILERS MUST BE INSTALLED IN ROOMS THAT MEET THE FUNDA-
B
MENTAL VENTILATION REQUIREMENTS. OTHERWISE THERE IS DANGER
OF SUFFOCATION OR INTOXICATION.
READ THE INSTALLATION AND MAINTENANCE INSTRUCTIONS BEFORE
INSTALLING THE UNIT.
ALSO FOLLOW THE DESIGN INSTRUCTIONS.
IN CASE OF PRESSURES ABOVE 200 Pa INSIDE THE FUME EXHAUST PI-
PES, CLASS "H1" FLUES MUST BE USED.
Important
The unit is "type C" with sealed chamber and forced draught; the air inlet and fume outlet must be connected to one of
the following extraction/suction systems. Before installation, check and carefully observe the above prescriptions. Also,
comply with the provisions concerning the positioning of wall and/or roof terminals and the minimum distances from win-
dows, walls, vents, etc.
Installation type C10
In case of flues under pressure in a collective flue, before installation and at subsequent maintenance operations, close
the fume discharge duct coming from the flue. OTHERWISE THERE IS DANGER OF SUFFOCATION DUE TO PRO-
DUCTS OF COMBUSTION ESCAPING INTO THE BOILER ROOM.
Installation of the boiler according to type C10 must be carried out by specialist personnel doing the calcula-
tions required by current regulations in compliance with the maximum positive pressure of the flue and the
boiler.
EN
Contact open disables DHW and re-enables it if closed.
Contact open disables heating and displays F50. Contact closed enables heating.
The contact acts as a room thermostat.
Contact open displays F51 and the boiler continues to operate.
It is used as an alarm.
The contact acts as a limit thermostat, if open it displays F53 and turns off the request.
Contact open puts the boiler in ECO mode.
Contact closed puts the boiler in COMFORT mode.
Contact open disables heating and displays F50.
Contact closed enables heating.
The contact acts as a room thermostat
Contact open displays F51 and the boiler continues to operate.
It is used as an alarm.
The contact acts as a limit thermostat, if open it displays F53 and turns off the request.
cod. 3541C662 - Rev. 00 - 09/2020