Electrical Characteristics - Fujitsu AOUG09LZAH1 Design & Technical Manual

Hide thumbs Also See for AOUG09LZAH1:
Table of Contents

Advertisement

10. Electrical characteristics

Model name
Voltage
Power
supply
Frequency
MCA *1
Starting current
MAX. CKT. BKR *3
Power cable
Wiring
spec. *2
Connection
cable *4
*1: Minimum Circuit Ampacity (Calculation based on UL60335-2-40)
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Maximum Circuit Breaker
*4: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
AOUG09LZAH1
V
Hz
A
A
A
AWG
Size
AWG
Limited
wiring
ft (m)
length
AOUG12LZAH1
208/230~
60
14.4
3.3
4.7
15
14
14
69 (21)
- 68 -
AOUG15LZAH1
17.5
5.2
20