Refrigerant System Pressure Access Ports - Carrier 50GCQ Series Service And Maintenance Instructions

Single package rooftop heat pump with puron® (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

Clamp
TXV Sensing Bulb
NOTE: Sensing bulb insulation removed for clarity.
Fig. 20 — TXV Valve and Sensing Bulb Location
SEAT
5/8" HEX
0.47
1. Third-party trademarks and logos are property of their respective owners.
Thermostatic
Expansion
Valve (TXV)
1/2-20 UNF RH
0.596
30°
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
Fig. 21 — CoreMax

Refrigerant System Pressure Access Ports

There are 2 access ports in the system: on the suction tube near the
compressor and on the discharge tube near the compressor. These
are brass fittings with black plastic caps. The hose connection fit-
tings are standard 1/4 in. SAE male flare couplings.
The brass fittings are 2-piece high flow valves, with a receptacle
base brazed to the tubing and an integral spring-closed check
valve core screwed into the base. See Fig. 21. This check valve is
permanently assembled into this core body and cannot be serviced
separately; replace the entire core body if necessary. Service tools
are available from RCD that allow the replacement of the check
valve core without having to recover the entire system refrigerant
charge. Apply compressor refrigerant oil to the check valve core's
bottom o-ring. Install the fitting body with 96 ± 10 in.-lb (10.85 ±
1.1 Nm) of torque; do not over-tighten.
CORE
(Part No. EC39EZ067)
Washer
O-Ring
1/2" HEX
®1
Access Port Assembly
14
45°
Depressor per AHRI 720
+.01/–.035
From Face of Body
7/16-20 UNF RH