Field Setting; Field Setting Switches; Dip Switch Setting - Fujitsu AirStage AJ 072GALDH Series Installation Manual

Table of Contents

Advertisement

Operation behavior
Each input terminal works as follows.
Input
Connector
signal
OFF
Input 1
CN131 (Yellow)
ON
OFF
Input 3
CN133 (White)
ON
OFF
Input 4
CN134 (Red)
ON
No pulse
Input 5
CN135 (Orange) (*3)
Pulse
Subordinate unit can connect only input5 (CN135).
The operations of each input terminal and the selection of function are set with the push
button on the PC board of outdoor unit. About the setting, please refer to "7.4. Push button
setting".
NOTES:
*1: The "external input priority mode" must be set by pressing push button on PC board
of outdoor unit. (Refer to "7. FIELD SETTING".)
*2: Batch stop or Emergency stop pattern can be selected by outdoor unit PC board
push button. (Refer to "7. FIELD SETTING".)
*3: The emergency stop function mounted in this model does not guarantee the
regulations of each country. For this reason, sufficient checking is necessary
regarding use.
Especially, since the fact that the equipment may not be emergency-stopped in the
case of breaking of the wiring to the external input terminals and communication
line, communication error due to noise, VRF external input circuit trouble, etc. must
be considered, the provision of double measures that add direct interruption of the
power supply by switch, etc. is recommended as a precaution.
6.7.3 External output terminal (primary unit only)
• You can detect the operation condition of outdoor unit and the abnormal situation of both
indoor and outdoor unit.
• The external output terminal is only valid for primary unit.
Wiring method and specifications
Error status
This output indicates the outdoor unit
and connected indoor unit's "Normal" or
"Error" status.
Operation status
This output indicates the outdoor unit's
"Operation" status.
P.C.B.
CN136 (Black) or
CN137 (Blue)
*1: Provide a DC 12 to 24 V power supply.
Select a power supply capacity with an ample surplus for the connected load.
*2: The allowable current is 30 mA or less.
Provide a load resistance such that the current becomes 30 mA or less.
*3: Polarity is [+] for pin 1 and [-] for pin 2. Connect correctly.
Do not impress a voltage exceeding 24 V across pins 1-2.
* A twisted pair cable (0.33 mm² (22AWG)) should be used.
Maximum length of cable is 150 m.
* Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
6.7.4 Base heater terminal
This is the output signal for base heater. Output signal ON, when the outdoor temperature
goes down below 2°C, and signal OFF at the outdoor temperature 4°C.
P.C.B.
Voltage:
CN115
power supply input voltage
(Black)
(*1)
Cable
(0.82 mm² (18AWG))
*1: Connect to pin 1 and pin 3. No connection pin 2 and pin 4.
*2: The allowable current is 1 A or less.
En-15
Outdoor unit
Status
Primary
Normal operation
Low noise mode operation
Normal operation
Outdoor unit operation peak
control
Normal operation
Batch stop or Emergency stop
operation (*1, *2)
No information from electricity
meter
Power usage information from
electricity meter
Output
Connector
voltage
Output 1
0 V
Normal
CN136
DC 12-24 V
Error
(Black)
(*1)
Output 2
0 V
Stop
CN137
DC 12-24 V
Operation
(Blue)
(*1)
DC power supply
(External) 12-24 V
Connected load (Operation Indica-
tor or Error Indicator)
Connected unit
Base heater (*2)

7. FIELD SETTING

Subor-
Discharge the static electricity from your body before setting up the DIP switches.
dinate
Never touch the terminals or the patterns on the parts that are mounted on the PC
board.
O

7.1. Field setting switches

O
Remove the service panel of the outdoor unit and the cover of the electrical component
box to access the PC board of the outdoor unit.
PC board switches for various settings and LED displays are shown in the figure.
O

7.2. DIP switch setting

7.2.1 List of Settings
O
O
SET3 and SET5 must be set for the
DIP switch.
Configure the settings before turning
on the power. Settings for SET1,
SET2, and SET4 DIP switches are
factory default ones. Do not change
them.
Status
Outdoor unit PC board
7.2.2 Settings to be confi gured locally
(1) Outdoor unit address setting
When 2 or 3 outdoor
units are installed to 1
refrigerant system, set the
address for each outdoor
unit.
Set the address for all
outdoor units.
(2) Number of subordinate units setting for outdoor unit
Set the number of subor-
dinate units connected to
1 refrigerant system.
Set only the primary unit.
(3) Number of outdoor units installed
The number of outdoor
units installed in 1 refriger-
ant system must be set.
Set for all outdoor units.
CAUTION
DIP Switch
SET 1
1-4
Prohibited
SET 2
1-4
Prohibited
1
Outdoor unit address setting
2
SET 3
3
Setting for number of subordi-
4
nate units
SET 4
1-4
Prohibited
Number of outdoor units
1-2
installed
SET 5
3
Prohibited
4
Terminal resistor setting
7 Segment
LED lamp
LED indicator
Push button
DIP switch
SET3
Outdoor unit
address
1
2
Primary unit
OFF
OFF
0
(Factory setting)
OFF
ON
1
Subordinate unit 1
ON
OFF
2
Subordinate unit 2
ON
ON
-
Prohibited
SET3
Number of
connectable
3
4
outdoor units
Primary unit only
OFF
OFF
0
(Factory setting)
1 subordinate unit con-
OFF
ON
1
nected
2 subordinate unit con-
ON
OFF
2
nected
ON
ON
-
Prohibited
SET5
Number of
outdoor units
1
2
OFF
OFF
1
(Factory setting)
OFF
ON
2
ON
OFF
3
ON
ON
-
Prohibited
Function
Rotary switch
Remarks
Remarks
Remarks
-
-