F. Protective Metal Hearth Strips
WARNING! Risk of Fire!
strips MUST be installed on combustible surfaces. DO
NOT cover metal strips with combustible materials.
Sparks or embers may ignite flooring.
WARNING! Risk of fire!
embers or other burning material falling from the
fireplace may ignite flooring or concealed combustible
surfaces.
Protective metal hearth strips MUST be installed.
Hearth extensions MUST be installed exactly as
specified.
Locate the two protective metal hearth strips measuring
approximately 26 in. x 4 in. (660 mm x 102 mm) included
with this fireplace.
Slide each metal strip 2 in. (51 mm) under front edge of
fireplace.
Overlap strips in the middle of fireplace opening by 1 in.
(25 mm) minimum.
Metal strips must extend beyond the front and sides
of the fireplace opening by at least 2 in. (51 mm),
Figure 3.6).
Protect the front of a platform elevated above the hearth
extension with metal strips (not included with fireplace)
per Figure 3.7. See
instructions.
14
Protective metal hearth
High temperatures, sparks,
Section 6
for hearth extension
Heatilator • Birmingham 36-B Installation Manual • 4059-709 • Rev AB • 06/23
1 in. (25 mm) overlap
Minimum
Metal strips are placed 2 in. (51 mm)
under the front of the fireplace and must
extend beyond the front and sides of
fireplace opening by 2 in. (51 mm).
Figure 3.6
Position the Protective Metal Hearth Strips
Top piece must overlap
Raised Platform
2 in.
(51 mm)
2 in.
(51 mm)
Figure 3.7
Protect the Front of an Elevated Platform
G. Outside Air Kit (Required on both sides)
Outside air kits must be used for combustion and to pro-
vide cooling air to prevent overheating. Hearth & Home
Technologies recommends you utilize the shortest duct run
to optimize the performance of the outside air kit and in-
stall a P-Trap (see Figure 3.10). The outside air inlet hoods
should be positioned in a manner that will not allow snow,
leaves, etc. to block the inlet. In some installations the air
duct may need to be run vertically. In such an installation,
a 3 ft (914 mm) height difference must be maintained from
the top of the uppermost chimney section to the outside air
inlet hoods.
Note: Maximum length is 40 feet.
bottom piece
1 in. (25 mm) min.
overlap
Floor