Mitsubishi TPKA0A0241KA80A Service Manual page 13

Table of Contents

Advertisement

• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD. (Refer to the previous page, 1 check code.)
● If the unit cannot be operated properly after test run, refer to the following table to find the cause.
Wired remote controller
Please Wait
Please Wait → Check code
Display messages do not
appear even when operation
switch is turned ON (operation
lamp does not light up).
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microprocessor)
LED2 (power for remote controller)
LED3 (communication between indoor and outdoor units)
TCHT011
Symptom
LED 1, 2 (PCB in outdoor unit)
For about 3
After LED 1, 2 are lit, LED 2 is turned
minutes after
off, then only LED 1 is lit.
power-on
(Correct operation)
Only LED 1 is lit.
→ LED 1, 2 blink.
Subsequent to
about 3 minutes
after power-on
Only LED 1 is lit.
→ LED 1 blinks twice,
LED 2 blinks once.
Indicates whether control power is supplied. Make sure that this LED is
always lit.
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant addresses "0".
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
• For about 3 minutes following power-on, operation
of the remote controller is not possible
due to system startup. (Correct operation)
• Connector for the outdoor unit's protection device
is not connected.
• Reverse or open phase wiring for the outdoor
unit's power terminal block (L1, L2, GR).
• Incorrect wiring between indoor and outdoor units
(incorrect polarity of S1, S2, S3)
• Remote controller wire short
13