START: Measure outdoor ambient temperature
USE WEIGH-IN METHOD
Weigh-in or remove refrigerant
based upon line length
ºF*
40
45
50
55
60
65
70
75
80
85
90
95
100
105
If
refrigerant
is
110
REMOVED, retest to
115
confirm that unit is
properly charged.
* Dry−bulb temperature (ºF) of entering outdoor ambient air.
If value is LESS than
shown, then REMOVE
refrigerant.
Figure 23. Using HFC−410A Superheat (Fixed Orifice) Charge Method
°F
Psig
°F
Psig
32
100.8
48
137.1
33
102.9
49
139.6
34
105.0
50
142.2
35
107.1
51
144.8
36
109.2
52
147.4
37
111.4
53
150.1
38
113.6
54
152.8
39
115.8
55
155.5
40
118.0
56
158.2
41
120.3
57
161.0
42
122.6
58
163.9
43
125.0
59
166.7
44
127.3
60
169.6
45
129.7
61
172.6
46
132.2
62
175.4
47
134.6
ABOVE or
BELOW
39ºF and
BELOW
SHº (Superheat) Values (+/−5ºF)
Wet Bulb (air entering indoor coil)
50 52 54 56 58 60 62 64 66 68 70 72 74 76
15 18 20 23 26 29 32 34 38 41 43 46 48 51
13 16 18 21 24 27 30 33 36 39 41 44 46 49
11 14 16 19 22 25 28 31 34 37 39 42 44 47
9 12 14 17 20 23 27 30 33 36 38 40 42 44
7 10 12 15 18 21 24 27 30 33 35 38 40 43
-
6 10 13 16 19 21 24 27 30 33 36 38 41
-
-
7 10 13 16 19 21 24 27 30 33 36 39
-
-
-
6
9 12 15 18 21 24 28 31 34 37
-
-
-
-
5
8 12 15 18 21 25 28 31 35
-
-
-
-
-
-
8 11 15 19 22 26 30 33
-
-
-
-
-
-
5
9 13 16 20 24 27 31
-
-
-
-
-
-
-
6 10 14 18 22 25 29
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
MORE or
LESS
Table 3. HFC−410A Temperature (°F) − Pressure (Psig)
°F
Psig
°F
Psig
63
178.5
79
231.6
64
181.6
80
235.3
65
184.3
81
239.0
66
187.7
82
242.7
67
190.9
83
246.5
68
194.1
84
250.3
69
197.3
85
254.1
70
200.6
86
258.0
71
203.9
87
262.0
72
207.2
88
266.0
73
210.6
89
270.0
74
214.0
90
274.1
75
217.4
91
278.2
76
220.9
92
282.3
77
224.4
93
286.5
78
228.0
1. Confirm proper airflow across coil using figure 19.
40ºF
2. Compare unit pressures with table 4, Normal
and
ABOVE
3. Use SUPERHEAT to correctly charge unit or to
4. Set thermostat to call for heat (must have a cooling
5. Connect gauge set.
6. When heat demand is satisfied, set thermostat to
7. Allow temperatures and pressures to stabilize.
8. Measure the suction line pressure and use the use
9. Record suction line temperature:
10. Subtract to determine superheat (SHº):
11. Record the wet bulb temperature (air entering
12. Record outdoor ambient temperature.
13. Compare results with table to the left.
8 12 16 21 24 28
5
9 13 17 22 26
NOTE − Do not attempt to charge system where a
-
6 11 15 20 25
dash appears, system could be overcharged.
Superheat is taken at suction line service port.
-
-
8 14 18 24
Suction line superheat must never be less than 5ºF
at the suction line service port.
If value is MORE
than shown, then
ADD refrigerant.
°F
Psig
°F
94
290.8
110
95
295.1
111
96
299.4
112
97
303.8
113
98
308.2
114
99
312.7
115
100
317.2
116
101
321.8
117
102
326.4
118
103
331.0
119
104
335.7
120
105
340.5
121
106
345.3
122
107
350.1
123
108
355.0
124
109
360.0
Page 25
Operating Pressures.
verify the charge is correct.
load between 70-80ºF (21−26ºC)
call for cooling.
value to determine saturation temperature (table
3):
SATº =_________
VAPº =_________
VAPº − _____ SATº ______ = SHº______
indoor coil):
WB =_______
If
refrigerant
is
ADDED, retest to
confirm that unit is
properly charged.
Psig
°F
Psig
365.0
125
445.9
370.0
126
451.8
375.1
127
457.6
380.2
128
463.5
385.4
129
469.5
390.7
130
475.6
396.0
131
481.6
401.3
132
487.8
406.7
133
494.0
412.2
134
500.2
417.7
135
506.5
423.2
136
512.9
428.8
137
519.3
434.5
138
525.8
440.2
139
532.4
140
539.0
°F
Psig
141
545.6
142
552.3
143
559.1
144
565.9
145
572.8
146
579.8
147
586.8
148
593.8
149
601.0
150
608.1
151
615.4
152
622.7
153
630.1
154
637.5
155
645.0
XC13 SERIES