Mitsubishi Electric CITY MULTI PFFY-P20VLEM-E Technical & Service Manual page 16

Floor standing type
Table of Contents

Advertisement

7-2. Setting of address switch
< At delivery (All models)>
ON
OFF
0 1 2
G
1
2 3
SW1
JP1
FP-AD-R
3
2
1
SWA
SWC
1)In case using network remote controller, address is set by rotary switches.(SW11,SW12)
* It is not necessary setting address in case of using unit remote controller.
Indoor unit do not run without address setting in field.
2) Indoor unit address setting rule is different by each field work.
Refer to install manual of outdoor unit , operate the address setting.
3)Setting the address is combination of SW11(1st digit address setting) and SW12(2nd digit address setting).
Address " 3 " setting is composed SW11 " 3 " and SW12 " 0 " .
Address " 25 " setting is composed SW11 " 5 " and SW12 " 2 " .
15
Indoor unit control board
SW2
SW 3
SW1
1 2 3 4 5 6 7 8 9 10
3 4 5 6 7 8 9
ON
ON
8
1
2
3
4
5
6
7
8
9 10
CN82
1
10
SW12
SW11
SW14
SW5
Make sure that power source is turning off.
S W 4
S W 4
ON
< At delivery (All models)>
OFF
1 2
3
4
5
1
6
1
CN62
ON
SW7
1
3
Refer to the next page for SW2,SW3 setting.
JP2
W254665G06
A B C D E F

Advertisement

Table of Contents
loading

Table of Contents