Custom Code Setting; Static Pressure Mode; Switching Of Airfl Ow Direction Louver Function - Fujitsu AIRSTAGE ARUL4TLAV1 Installation Manual

Hide thumbs Also See for AIRSTAGE ARUL4TLAV1:
Table of Contents

Advertisement

Setting
Setting
range
Indoor unit address
0 to 63
Refrigerant circuit
0 to 99
address
(1) Indoor unit address
Rotary switch (IU AD × 1)...Factory setting "0"
Rotary switch (IU AD × 10)...Factory setting "0"
When connecting multiple indoor units to 1 refrigerant system, set the address at IU AD
SW as shown in the Table A.
(2) Refrigerant circuit address
Rotary switch (REF AD × 1)...Factory setting "0"
Rotary switch (REF AD × 10)...Factory setting "0"
In the case of multiple refrigerant systems, set REF AD SW as shown in the table below
for each refrigerant system.
Set to the same refrigerant circuit address as the outdoor unit.
• If working in an environment where the wireless remote controller can be used, the ad-
dresses can also be set using the remote controller.
• If setting the addresses using the wireless remote controller, set the indoor unit address
and refrigerant circuit address to "00".
(For information on setting using the wireless remote controller.)
Rotary switch
Address
REF AD SW
Refrigerant circuit
× 10
0
0
1
0
2
0
3
0
4
0
5
0
6
0
7
0
8
0
9
0
10
1
11
1
12
1
.
.
.
.
.
.
99
9
Do not set the indoor unit address (IU AD SW) at 64 to 99.
It may result in failure.
(3) Remote controller address
i) 3-wire type
Rotary switch (RC AD SW)...Factory setting "0"
When connecting multiple indoor units to 1 standard wired remote controller, set the ad-
dress at RC AD SW in sequence from 0.
Setting
Setting range
Remote controller
0 to 15
address
Example
If 4 indoor units are connected.
Indoor unit
Indoor unit
RC AD SW
RC AD SW
0
1
Remote
controller
RC AD
0
1
2
3
4
SW
Address
0
1
2
3
4
En-13
Type of switch
Setting
example 2
IU AD × 10
Setting
example 63
REF AD × 10
Address
setting
Indoor unit
× 1
× 10
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
0
10
1
11
2
12
.
.
.
.
.
.
9
63
Type of switch
Setting
example
0
RC AD
Indoor unit
Indoor unit
RC AD SW
RC AD SW
2
3
5
6
7
8
9
A
B
5
6
7
8
9
10
11
ii) 2-wire type
Rotary switch (RC AD SW)...Factory setting "0"
Since the remote controller address settings are automatically configured, you do not
need to configure them.
If configuring manually, it is necessary to configure both the indoor unit and the remote
controller.
For details, please refer to the remote controller manual.
IU AD × 1

7.2. Custom code setting

• Selecting the custom code prevents the indoor unit mix-up. (figure below)
(Up to 4 codes can be set.)
• Perform the setting for both the indoor unit and the remote controller.
REF AD × 1
Indoor unit
Remote
controller
• Custom code setting for indoor unit
Set the DIP switch SET3 SW1, 2, referring to the
figure and table below.
ON
OFF
Rotary switch
setting
IU AD SW
× 1

7.3. Static pressure mode

0
0
0
1
0
2
If the applicable static pressure does not match the static pressure mode, the static
0
3
pressure mode may be changed to another mode manually.
0
4
0
5
0
6
0
7
0
8
0
9
It is necessary to set up a static pressure mode for each usage of static pressure.
1
0
Static pressure can be set at site.
Relation between set values and static pressure are as the following table.
1
1
• FUNCTION SETTING can be performed with the wired or wireless remote controller.
1
2
(The remote controller is optional equipment)
.
.
• Refer to the wired or wireless remote controller manual for detailed setting information.
.
.
.
.
6
3
Function Number
If set to "04" through "30", setting static pressure becomes 0.12 in WG (30 Pa).
7.4. Switching of airfl ow direction louver function
When auto louver grille (Optional parts) is attached, set the airfl ow direction louver func-
tion "Valid".
The airfl ow direction louver of auto louver grille can be operated by the remote controller
while the airfl ow direction louver function is valid.
• Installation method
Set the DIP switch SET 4 SW2, SW2 referring to the
table below.
ON
OFF
C
D
E
F
12
13
14
15
Confusion
DIP switch "SET3"
DIP switch
SET3
SW1
SW2
SW
SW
SW
SW
1
2
3
4
CAUTION
Recommended range of external static pressure
ARUL4: 0 to 0.36 in WG (0 to 30 Pa)
Setting Number
00
01
26
02
03
31
DIP switch "SET4"
DIP switch
SET4 SW2
SW
SW
SW
SW
1
2
3
4
Code change
A
B
C
D
A
B
C
D
IU AD
REF AD
RC AD
×10
×1
×10
×1
SET3
SET4
DIP switch "SET3"
Custom code
A (Factory
B
C
D
setting)
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Setting Static Pressure
0 in WG (0 Pa)
0.04 in WG (10 Pa)
0.08 in WG (20 Pa)
0.12 in WG (30 Pa)
0.04 in WG (10 Pa)
IU AD
REF AD
RC AD
×10
×1
×10
×1
SET3
SET4
DIP switch "SET4"
Airflow direction louver
OFF
function "Invalid" (Factory
setting)
Airflow direction louver
ON
function "Valid"