Carrier 38AUQ 25 Series Installation, Start-Up And Service Instructions Manual page 32

Heat pump condensing units with puron (r-410a) refrigerant
Table of Contents

Advertisement

Service Parts
Listings of service parts for all units are available from the Re-
placement Components Division's Electronic Parts Information
Catalog (EPIC). EPIC is available at Totaline
and
service
office
parts
HVACPartners.com.
When entering EPIC, the full unit model number is required. The
model number includes the Design Revision reference value (see
Fig. 3, Position 13). The unit model number is available from the
unit's information data plate. (Do not use the "catalog number"
when using EPIC. The "catalog number" suppresses the Design
Revision value; failure to include Design Revision value may
cause an incorrect unit parts list to be displayed.) When using
EPIC, enter first four digits of the model number only. Find appro-
priate model from sales packages listed. Be sure to choose correct
voltage and Design Revision.
EPIC is a product of RCD. To comment of the EPIC program, use
the "Comment" button inside the EPIC program.
®
stores, distributor
departments
and
online
FASTENER TORQUE VALUES
Compressor mounting bolts
at
Condenser fan motor mounting bolts
Condenser fan hub setscrew
High-flow service port
Schrader-type service check valve
Compressor oil sight glass thread
Compressor to Compressor rail torque
Compressor rail to base pan torque
32
65-75 in.-lb 
(734-847 N-cm)
20 ±2 in.-lb 
(226 ±23 N-cm)
84 ±2 in.-lb 
(949 ±136 N-cm)
96 ±10 in.-lb 
(1085 ±23 N-cm)
2-3 in.-lb 
(23-34 N-cm)
330±31 in.-lb
(23-34 N-cm)
120-168 in.-lb
(1356-1898 N-cm)
70 ±5 in.-lb 
(791 ±57 N-cm)