The Standard Range LightSpot is a sensitive, ultrasonic movement detector; it is essential therefore that it be installed on a rigid surface that will not itself be subject to movement or vibration.
Fix directly to a rigid surface or use the semi-flush fixing kit to recess into a ceiling tile etc. (For semi-flush fixing, use a hole saw to drill a 76mm hole into the ceiling tile.) Existing light switch can be retained. Use switch wire from switch as LIVE IN. A spare connection has been provided for earth termination.
Switching capacity 10 Amps. Incandescent lamps: 1500W max. For use on 230V ac supplies only.
Important Additional Notes
Ensure that any heating / ventilation plant which may cause interference is switched ON. Set the PHOTOCELL control fully clockwise, sensitivity controls fully anti-clockwise and the four switches to OFF then follow these simple commissioning instructions. We recommend that the Off Sensitivity is not adjusted unless absolutely necessary and therefore the commissioning procedure is started from Step 2.
ON | OFF | ||
1 | Power-up ON | Power-up OFF | |
2 | Semi-auto | Auto | |
3 | 5 min delay | Zero delay | Add switches together to select 15 minutes |
4 | 10 min delay | Zero delay |
SENSITIVITY CONTROLS
ON Sensitivity - Sets sensitivity to movement when lights are switched on "
This is the normal sensitivity adjustment expected on any detector. Choose a setting as low as practical. (ON Sensitivity set to maximum will result in lights staying on permanently.)
OFF Sensitivity - Sets sensitivity to movement when lights have switched off
This additional sensitivity adjustment is useful in storage aisles, open plan areas etc. It enables a reduced sensitivity to be set for when an area is empty, so that fringe activity will not switch on the lights. When fully clockwise, a very large movement is needed to switch on the lights whilst a much smaller movement (set by ON Sensitivity) will sustain them. In enclosed rooms or corridors, this control may be left in the fully anti-clockwise position when the sensitivity will remain the same whether the lights are ON or OFF. The change takes 5 seconds after the lights have switched off to establish fully.
OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 5 metres
SWITCH CAPACITY: 10 Amps. Incandescent lamps: 1500W max (at 230V)
TERMINAL CAPACITY: 2 x 1.5mm or 1 x 2.5mm
WEIGHT: 148g
TIME DELAY: 5, 10 or 15 mins
POWER-UP CONDITION: select ON or OFF
DETECTOR RANGE: adjustable - see installation notes
RANGE REDUCTION: adjustable - see installation notes
ULTRASONIC FREQUENCY: 40kHz
PHOTOCELL: adjustable 50 to 5000 lux
SEMI-FLUSH FIXING: requires 76mm hole to be drilled in ceiling tile
Ex-Or
Novar ED&S Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ
Tel: +44 (0)1942 719229
Fax: +44 (0)1942 508753
Email: technicalsales.ex-or@honeywell.com
At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Download Honeywell MS1500P, MS1500PF - Installation And Commissioning Manual