Lennox G21Q Series Installation Instructions Manual page 15

Hide thumbs Also See for G21Q Series:
Table of Contents

Advertisement

Nominal
Nominal
Internal
Internal
Iron Pipe Size
Diameter
- -Inches(mm)
- -Inches(mm)
1/4
.364
(6.35)
(9.246)
3/8
.493
(9.53)
(12.522)
1/2
.622
(12.7)
(17.799)
3/4
.824
(19.05)
(20.930)
1
1.049
(25.4)
(26.645)
1- -1/4
1.380
(31.75)
(35.052)
1- -1/2
1.610
(38.1)
(40.894)
2
2.067
(50.8)
(52.502)
2- -1/2
2.469
(63.5)
(67.713)
3
3.068
(76.2)
(77.927)
4
4.026
(101.6)
(102.260)
NOTE- -Capacity given in cubic feet (m
The above connectors may be used if acceptable
by the authority having jurisdiction. A gas connec-
tor is provided and, if used, should be installed be-
tween the manual main shut- -off valve and ground
joint union. See figure 19 for correct piping.
3 - - Center gas line through piping hole.
should not touch side of unit.
4 - - Connect gas supply line.
MANUAL MAIN
SHUT- -OFF VALVE
1/8” (3.2mm)
N.P .T.
PLUGGED
GAS CONNECTOR*
TAP
RIGHT SIDE PIPING
(STANDARD)
GAS VALVE
GAS CONNECTOR*
*Gas connector may be used for Canadian installation if acceptable by local authority
having jurisdiction.
FIGURE 19
GAS PIPE CAPACITY - - FT
10
20
(3.048)
(6.096)
43
29
(1.13)
(.82)
95
65
(2.69)
(1.84)
175
120
(4.96)
(3.40)
360
250
(10.19)
(7.08)
680
465
(19.25)
(13.17)
1400
950
(39.64)
(26.90)
2100
460
(59.46)
(41.34)
3950
2750
(111.85)
(77.87)
6300
4350
(178.39)
(123.17)
11000
7700
(311.48)
(218.03)
23000
15800
(651.27)
(447.39)
!
) of gas per hour and based on 0.60 specific gravity gas.
LEFT SIDE PIPING
GAS VALVE
GROUND JOINT
UNION
MANUAL MAIN
SHUT- -OFF VALVE
GROUND JOINT
UNION
1/8” (3.2mm)
N.P .T.
PLUGGED TAP
TABLE 5
!
/HR (kL/HR)
Length of Pipe- -Feet(m)
30
40
50
(9.144)
(12.192)
(15.240)
24
20
18
(.68)
(.57)
(.51)
52
45
40
(1.47)
(1.27)
(1.13)
97
82
73
(2.75)
(2.32)
(2.07)
200
170
151
(5.66)
(4.81)
(4.28)
375
320
285
(10.62)
(9.06)
(8.07)
770
660
580
(21.80)
(18.69)
(16.42)
1180
990
900
(33.41)
(28.03)
(25.48)
2200
1900
1680
(62.30)
(53.80)
(47.57)
3520
3000
2650
(99.67)
(84.95
(75.04)
6250
5300
4750
(176.98)
(150.07)
(134.50)
12800
10900
9700
(362.44)
(308.64)
(274.67)
Flexible gas connec
the unit. Flex connector must be installed in U- -
shaped fashion in order to achieve its purpose
Gas line
(See figure 19). Do not secure to unit ducting or
structure.
B - - Leak Check
After gas piping is completed, carefully check all piping
connections (factory- - and field- -installed) for gas leaks.
Use a leak detecting solution or other preferred means.
6RPH VRDSV XVHG IRU OHDN GHWHFWLRQ DUH FRUURVLYH
WR FHUWDLQ PHWDOV &DUHIXOO\ ULQVH SLSLQJ WKRURXJKO\
DIWHU OHDN WHVW KDV EHHQ FRPSOHWHG 'R QRW XVH
PDWFKHV FDQGOHV IODPH RU RWKHU VRXUFHV RI LJQL
WLRQ WR FKHFN IRU JDV OHDNV
7KH IXUQDFH PXVW EH LVRODWHG IURP WKH JDV VXSSO\
V\VWHP E\ FORVLQJ LWV LQGLYLGXDO PDQXDO VKXW RII
YDOYH GXULQJ DQ\ SUHVVXUH WHVWLQJ RI WKH JDV VXSSO\
SLSLQJ V\VWHP DW WHVW SUHVVXUHV HTXDO WR RU OHVV
WKDQ  SVLJ  N3D 
7KH IXUQDFH DQG LWV LQGLYLGXDO VKXW RII YDOYH PXVW
EH GLVFRQQHFWHG IURP WKH JDV VXSSO\ SLSLQJ V\V
WHP GXULQJ DQ\ SUHVVXUH WHVWLQJ RI WKH V\VWHP DW
WHVW SUHVVXUHV JUHDWHU WKDQ  SVLJ  N3D 
3DJH 
60
70
80
(18.288)
(21.336)
(24.384)
16
15
14
(.45)
(.42)
(.40)
36
33
31
(1.02)
(.73)
(.88)
66
61
57
(1.87)
(1.73)
(1.61)
138
125
118
(3.91)
(3.54)
(3.34)
260
240
220
(7.36)
(6.80)
(6.23)
530
490
460
(15.01)
(13.87)
(13.03)
810
750
690
(22.94)
(21.24)
(19.54)
1520
1400
1300
(43.04)
(39.64)
(36.81)
2400
2250
2050
(67.96)
(63.71)
(58.05)
4300
3900
3700
(121.76)
(110.43)
(104.77)
8800
8100
7500
(249.18)
(229.36)
(212.37)
CAUTION
tor must not be used to exit
&$87,21
,03257$17
90
100
(27.432)
(30.480)
13
12
(.37)
(.34)
29
27
(.82)
(.76)
53
50
(1.50)
(1.42)
110
103
(3.11)
(2.92)
205
195
(5.80)
(5.52)
430
400
(12.18)
(11.33)
650
620
(18.41)
(17.56)
1220
1150
(34.55)
(32.56)
1950
1850
(55.22)
(52.38)
3450
3250
(97.69)
(92.03)
7200
6700
(203.88)
(189.72)