Siemens RUGGEDCOM RS8000T Installation Manual page 39

Hide thumbs Also See for RUGGEDCOM RS8000T:
Table of Contents

Advertisement

RUGGEDCOM RS8000T
Installation Guide
IEEE 1613 (C37.90.x) EMC Immunity Type Tests
NOTE
The RUGGEDCOM RS8000T meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
IEEE Test
IEEE 1613 Clause
C37.90.3
C37.90.2
C37.90.1
C37.90
Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
EMC and Environmental Type Tests
9
ESD
8
Radiated RFI
7
Fast Transient
Oscillatory
6
HV Impulse
Dielectric
Strength
Description
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
Vibration
Shock
Description
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Test Levels
Test Ad
-40 °C (-40 °F), 16 Hours
Test Bd
85 °C (185 °F), 16 Hours
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
2 g @ 10-150 Hz
30 g @ 11 ms
Chapter 6
Certification
Test Levels
±8 kV
±15 kV
35 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV
±4 kV
2.5 kV common mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
2.5 kV common and
differential mode @ 1MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kVAC (Failsafe Relay)
1.5 kVDC
2 kVAC
Severity Levels
Class 2
Class 2
29