Part Load Performance - Mitsubishi Electric PUHY-P250YHM-A Data Book

Hide thumbs Also See for PUHY-P250YHM-A:
Table of Contents

Advertisement

2-3. Part Load Performance

10HP System
Indoor Unit
: PFD-P250VM-E
Outdoor Unit : PUHY-P250YHM-A
Outdoor unit inlet
Cooling
temp. (˚CDB)
Capacity (kW)
40 ˚C
35 ˚C
30 ˚C
25 ˚C
20 ˚C
15 ˚C
20HP System
Indoor Unit
: PFD-P500VM-E
Outdoor Unit : PUHY-P250YHM-A
Outdoor unit inlet
Cooling
temp. (˚CDB)
Capacity (kW)
40 ˚C
35 ˚C
30 ˚C
25 ˚C
20 ˚C
15 ˚C
100%
90%
Capacity
Capacity
26.6
10.05
8.75
28.0
9.30
8.11
29.4
8.65
7.61
30.2
8.10
7.21
31.1
7.72
6.92
31.6
7.54
6.87
2
100%
90%
Capacity
Capacity
53.2
20.09
17.46
56.0
18.60
16.19
58.8
17.30
15.24
60.5
16.19
14.47
62.2
15.44
13.88
63.3
15.07
13.83
System Power input (kW)
80%
70%
60%
Capacity
Capacity
Capacity
7.68
6.79
6.08
7.18
6.41
5.82
6.81
6.17
5.50
6.56
6.00
5.38
6.26
5.74
5.27
6.31
5.80
5.35
* Indoor air temperature condition: 27˚CDB/19˚CWB
System Power input (kW)
80%
70%
60%
Capacity
Capacity
Capacity
15.24
13.49
12.08
14.30
12.77
11.51
13.58
12.24
10.79
13.06
11.79
10.59
12.53
11.42
10.48
12.63
11.58
10.67
* Indoor air temperature condition: 27˚CDB/19˚CWB
5
50%
40%
Capacity
Capacity
5.50
5.04
5.13
4.60
4.94
4.52
4.89
4.50
4.85
4.47
4.94
4.56
50%
40%
30%
Capacity
Capacity
Capacity
10.94
10.07
8.37
10.11
9.05
8.06
9.76
8.92
7.68
9.67
8.79
7.55
9.64
8.52
7.49
9.84
8.62
7.64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pfd-p250vm-ePfd-p500vm-e

Table of Contents