5.Wiring Examples

For input/output circuit and other examples than below, refer to Safety Light Curtain F3SG-RR Series User's Manual.
5-1. EDM enabled, Auto Reset Mode, External Test in 24 V Active (not
used) and PNP Outputs
□□
F39-JD
KM1, KM2: Safety relay with forcibly guided contacts (G7SA)
M: 3-phase motor
*1. Connect the line to 24 V via a test switch (N.O. contact) if External Test is used.
*2. Connect a lockout reset switch (N.C. contact) to this line in series with the KM1 and KM2 if Lockout Reset is used.
*3. The F39-JD
RA-L Single-Ended Cable for Emitter (Oil-Resistant Extension Cable) does not have the red, white and yellow wires.
*4. For the F39-JD
A-
Single-Ended Cable, connect the shield line to 0 V.
5-2. EDM disabled, Auto Reset Mode, External Test in 24 V Active (not used),
Reduced Wiring Connector and PNP Outputs
The reduced wiring system can be achieved by using the Reduced Wiring Cables (F39-JD□BA) and the Reduced Wiring Connector
(F39-CN5).
F39-CN5
F39-JD□B-L
KM1 KM2
*1. For the F39-JD□A-□ Single-Ended Cable, connect the shield line to 0 V.
The F3SG-RR meets IP67 (IEC 60529) when it is correctly connected with the Cable for Reduced Wiring (F39-JD
Reduced Wiring Connector (F39-CN5). Keep the F3SG-RR from cutting oils when using these cables and connector.
□□□□
□□
F3SG-
RR
P
Quick Installation Manual
Wiring
□□
A-L *4
F39-JD
A-D *4
KM1 KM2
KM1
KM2
KM1
KM2
F39-JD□A-D *1
KM1, KM2: Safety relay with forcibly guided contacts (G7SA)
M: 3-phase motor
+24 VDC
Power Supply
0 VDC
-02TS
Mounting/Beam Alignment
[Settings]
EDM Enabled (factory default setting)
Receiver
Auto Reset (factory default setting)
PNP (factory default setting)
External Test: 24 V Active (factory
Emitter
default setting)
+24 VDC
Power Supply
0 VDC
[Settings]
EDM Enabled (factory default setting)
Receiver
Auto Reset (factory default setting)
PNP (factory default setting)
External Test: 24 V Active (factory
Emitter
default setting)
M
Operation check
Function
KM1
KM2
M
Function
BA) and
4