Page of 1
Download Bookmark Comment

Cooper Lighting SURE-LITES HR117 Specification Sheet

Cooper lighting emergency light specification sheet.
Hide thumbs
   
COOPER LIGHTING - SURE-LITES
®
D I M E N S I O N S
D E S C R I P T I O N
A real workhorse in emergency
lighting systems. These
durable, reliable units are
unparalleled in both
performance and freedom
B
G
from maintenance.
The HR Series provide a low
C
cost, solid-state lighting
system ideal for industrial,
commercial or multi-housing
HR SERIES
environments. High capacity
D
H
makes the HR Series ideal for
E
E
F
installations where a large
A
number of heads/exits will be
H i g h C a p a c i t y,
remotely operated.
8 7 - 1 1 7 W a t t s
High Capacity
Ultra High Capacity
U l t r a - H i g h C a p a c i t y
1 7 0 - 3 6 0 W a t t s
A
12 1/4" (311mm)
17" (432mm)
B
13 1/4" (337mm)
16 7/8" (429mm)
E M E R G E N C Y L I G H T
C
7 7/8" (200mm)
11 1/2" (292mm)
D
4 1/4" (108mm)
8" (203mm)
• Dual-voltage input
E
4 3/4" (121mm)
6" (152mm)
120/277VAC, 60Hz
F
1 3/8" (35mm)
2" (51mm)
G
-----------------------
5 3/4" (146mm)
• 18 gauge die formed steel
housing and cover
H
-----------------------
2 1/2" (64mm)
• White powder coat finish
• Two top mounted, fully
adjustable, white, high-
Impact thermoplastic
heads
E L E C T R I C A L R AT I N G S
• Sealed lead-calcium
Rated Wattage
Lamp Information
to 87 1/2% of rated D.C. Voltage
battery
Model
DC Voltage 1 1/2 hours
2 hours
3 hours
4 hours
Type
Wattage
Number
High Capacity
• Knockout, conduit or cord
HR87*
6
87
65
43
32
Incandescent 9
29-84
set
HR117*
6
117
87
58
43
Incandescent 9
29-84
HR12117*
12
117
87
58
43
Incandescent 9
29-86
• Line-latching, Solid-State
HR12117347*
1
12
117
87
Incandescent 9
29-86
voltage limited charger,
Ultra High Capacity
Solid-State switching, low-
HR180*
6
180
135
90
67
Incandescent 9
29-84
voltage disconnect,
HR12170*
12
170
128
85
64
Incandescent 9
29-86
brownout circuit,
HR12210*
12
210
157
105
78
Incandescent 9
29-86
overload/short-circuit
HR12360*
12
360
270
180
135
Incandescent 9
29-86
protection, test
switch/power indicator
*Batteries may be shipped separately.
light
• UL 924 Listed, CSA
O R D E R I N G I N F O R M AT I O N
E n e r g y D a t a
Certified, Life Safety NFPA
101, NEC/OSHA, most
Input Current (Max.):
S A M P L E N U M B E R : H R 8 7 T D M
state and local codes
Model No.
120V
277V
347V
HR87
.50A
.21A
HR117
.53A
.22A
HR12117
.26A
.13A
Options
Accessories
Model
HR12117347
.25A
.60A
Number
(Add as suffix)
(Order separately)
HR180
.98A
.43A
HR87
A=Ammeter
VK1 =Voltmeter
HR12170
1.08A
.45A
HR117
TDM=Time Delay Monitor
3BRWH =Mounting Brackets
HR12210
1.02A
.47A
HR12117
HR12360
1.17A
.54A
V=Voltmeter
2MSWH =Mounting Shelf
HR180
(High Capacity)
(2)
Alternate Lamps
HR12170
3MSWH =Mounting Shelf
Other Options
(2)
HR12210
(Ultra High Capacity)
Other finishes
(2)
HR12360
WG3=Wire Guard
MH=Metal heads
(Ultra High Capacity)
WG7=Wire Guard
(High Capacity)
CSK120=Cord Set (120VAC)
CSK277=Cord Set (277VAC)
VS2=Polycarbonate Vandal
Shield
VS2WP=Polycarbonate Vandal
Shield - Weatherproof
Note: 0, 1, 3 & 4 Heads also available. Specify after catalog number (i.e., HR-12117379)
622
COOPER LIGHTING
(1)
(2)
347=120/347V
Consult your Cooper Lighting Representative.