Air Evacuation

:
NOTE
PREPARATIONS AND PRECAUTIONS
Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can
damage the air conditioner, reduce its e ciency, and cause injury. Use a vacuum pump and manifold
gauge to evacuate the refrigerant circuit, removing any non-condensable gas and moisture from the
system. Evacuation should be performed upon initial installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
Make sure the connective pipes between the indoor and outdoor units are connected properly.
Check to make sure all wiring is connected properly.
Evacuation Instructions
Indoor unit
Outdoor unit
Pressure hose
Charge hose
Low pressure
Manifold
valve
-76cmHg
Compound
Pressure
gauge
gauge
Low
High
pressure
pressure
valve
valve
or
Charge
hose
valve
Step 1:
Connect the charge hose of the manifold
gauge to service port on the outdoor unit's
low pressure valve.
Connect another charge hose from the
manifold gauge to the vacuum pump.
Open the Low Pressure side of the manifold
gauge. Keep the High Pressure side closed.
Turn on the vacuum pump to evacuate the
system.
Run the vacuum for at least 15 minutes, or
until the Compound Meter reads -76cmHG
(-10 Pa).
Close the Low Pressure side of the manifold
gauge, and turn o the vacuum pump.
Wait for 5 minutes, then check that there
has been no change in system pressure.
Vacuum
pump
29
29