Large lcd digital thermostat 230 vac , floating output 2-pipe fan coil control

Advertisement

Backlight
Any key press will activate the backlight. Backlights
will timeout 8 seconds after last key press. When
in Installer Set-up and Installer test mode, the
backlight will timeout 60 seconds after last key
press.
Keypad lock
Keypad lock can be set in ISU with default status
is all keys available. You may change into mode
button locked out, Fan and mode buttons locked out
and All buttons locked out by changing the ISU.

Operating modes

The following operating modes are available:
Comfort mode
In comfort mode, the setpoint can be changed by
pressing up and down button. Different applications
include cool only, heat only and manual heat/cool
changeover.
Ventilation mode
Press mode button to enter ventilation mode. In
ventilation mode, no output for floating valve while
the fan will operate according to selected fan speed.
Remote temperature sensor
T6861 provides control either depending on the
acquired room temperature or depends on the return
air temperature. The model of remote temperature
sensor is (NTC20K).
INDICATES THERMOSTAT
HAS BEEN SET TIME OFF
TEMPERATURE
SETTING
PRESS THIS BUTTON TO
RAISE THE TEMPERATURE
SETTING
Freezing protection mode
Freezing protection can be selected as disabled
(default) or enabled. In freezing protection mode
(no such mode in cool only application), when
thermostat is in OFF mode while the acquired
o
temperature is below 6
heat mode until the temperature rises to 8
thermostat is turned on.
On/off mode
Pressing power button can switch between on and
off mode.

Technical specification

Power supply
230 (+10%, -10%) VAC
Frequency
50Hz
Control algorithm PI, floating output
o
Accuracy
+/-1
C at 21
Rating capacity
For 230V power supply:
10(2)A for fan load, 3(1)A for valve
Cycle times
100,000 times
Setpoint range
10~32
o
Display range
0~37
C
Installation
Installed on 86×86mm
junction box or 3×3 inch.
Protection Class IP20
Environmental
Operation temperature -18~49
Conditions
Shipping temperature -35~65
Relative humidity 5~90%,
noncondensing
C, the thermostat will start
o
C or the
INDICATES THERMOSTAT
HAS BEEN SET TIME OFF
o
C
o
C
o
o
C
C
3