Power
Model
• All-plastic (with integral 4/20 or 20/4 mA output),
General Purpose/Dust Ignition Proof.
• Enclosure or Integrated Cable (with integral 4/20
or 20/4 mA output), Intrinsically Safe Application.
• Solid State Output (with integral 4/20 or 20/4 mA output), 12–33 V DC
Non-intrinsically Safe Application.
Alarm Output(s):
• mA
• solid state switch
• relay output
• intrinsically safe
• repeatability
• conducted immunity
Environmental
• ambient temperature:
• ingress protection:
- enclosure version
- cable version
Mechanical
• common probe/wetted parts: PPS process connection and PPS sensor; or AISI 316 L
process connection and PPS or PVDF sensor.
(Standard Metal process connection seal is FPM. FFKM is optional)
• cable version:
• body / housing, 316 stainless steel
• process connection, 3/4" NPT or 1" BSPT
• enclosure version:
• body: impact proof VALOX®,
316 stainless steel option
• lid: translucent polycarbonate
1.
VALOX is a registered trademark of the General Electric Company.
Page EN-2
CLS 100
(all-plastic)
4/20 mA or 20/4 mA 2-wire current loop detection
not available
30 V DC, 2A, 60 W
110 V DC, 0.5 A, 60 W
125V AC, 0.5 A, 60 VA
not available
2 mm (0.08")
3 V/m
-40 to 85 °C (-40 to 185 °F)
Type 4X / NEMA 4X / IP68
Type 4X / NEMA 4X / IP65
1
Pointek CLS 100 – QUICK START MANUAL
Power Requirements
12–33 V DC
10–30 V DC
CLS 100 (enclosure
and integrated cable)
40 V DC / 28 V AC
100 mA max.
2 VA max.
not available
30 V DC max.
10 V/m
• installation category:
• pollution degree:
• 1 1m (3.3 ft) of 4 conductor, 22 AWG,
shielded, polyester jacket
• internal removable 5-point terminal
block
• ½" NPT wiring entrance
(optional M20 x 1½" cable entry)
II
4
7ML19985QJ81