York XA Series Installation Manual page 19

Table of Contents

Advertisement

XA-15, XA-20 - High Static Drive Without Powered Convenience Outlet
Compressors
Size
(each)
Volt
(Tons)
RLA LRA MCC
208-3-60 25
164
230-3-60 25
164
-15
(15)
460-3-60 12.2
100
575-3-60
9
78
208-3-60 34.3
239
230-3-60
-20
(20)
460-3-60 17.9
125
575-3-60 12.8
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Ducted Systems
OD Fan
Supply
Pwr
Motors
Blower
Conv
(each)
Motor
Outlet
FLA
FLA
FLA
39
4.1
20
0
39
3.9
19.4
0
19
2.15
9.7
0
14
1.6
7.8
0
52
3.4
26
3.4
25
28
1.8
12.5
20
1.4
10
Electric Heat
(Field Installed Accessory Only)
Model
kW
Stages
Amps
NONE
-
-
-
E18
13.5
1
37.5
E36
27
2
74.9
E54
40.6
2
112.7
E72
54.1
2
150.2
NONE
-
-
-
E18
18
1
43.3
E36
36
2
86.6
E54
54
2
129.9
E72
72
2
173.2
NONE
-
-
-
E18
18
1
21.7
E36
36
2
43.3
E54
54
2
65
E72
72
2
86.6
NONE
-
-
-
E18
18
1
17.3
E36
36
2
34.6
E54
54
2
52
E72
72
2
69.3
NONE
-
-
-
E18
13.5
1
37.5
E36
27
2
74.9
E54
40.6
2
112.7
E72
54.1
2
150.2
NONE
-
-
-
E18
18
1
43.3
E36
36
2
86.6
E54
54
2
129.9
E72
72
2
173.2
NONE
-
-
-
E18
18
1
21.7
E36
36
2
43.3
E54
54
2
65
E72
72
2
86.6
NONE
-
-
-
E18
18
1
17.3
E36
36
2
34.6
E54
54
2
52
E72
72
2
69.3
5168274-BIM-I-1121
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
84.5
100
131.3
150
131.3
150
165.9
175
178.1
200
83.5
100
137.6
150
137.6
150
154.2
175
197.5
225
41.5
50
68.5
70
68.5
70
77.1
90
98.7
110
31.3
40
52.9
60
53.1
60
61.7
70
79
90
116.8
150
163.7
175
163.7
175
173.4
175
210.4
225
115.8
150
169.9
175
169.9
175
169.9
175
224.1
225
60
70
87.1
90
87.1
90
87.1
90
114.1
125
44.4
50
66
70
66
70
66
70
87.7
90
19