Fujitsu AR 18LUAD Series Service Instruction page 70

Duct type inverter, refrigerant r410a, indoor/outdoor unit
Hide thumbs Also See for AR 18LUAD Series:
Table of Contents

Advertisement

Trouble shooting 10
INDOOR UNIT Error Method:
Indoor Fan Motor abnormal
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Fan Motor
Forecast of Cause:
1. Fan rotation failure 2. Fan motor winding open 3. Motor protection by surrounding temperature rise
4. Capacitor failure
Check Point 1 : Check rotation of Fan
Rotate the fan by hand when operation is off.
(Check if fan is caught, dropped off or locked motor)
>>If Fan or Bearing is abnormal, replace it.
OK
Check Point 2 : Check Motor winding
Check Indoor Fan motor. (PARTS INFORMATION 5)
>>If Fan motor is abnormal, replace it.
OK
Check Point 3 : Check ambient temp. around motor
Check excessively high temperature around the motor.
(If there is any surrounding equipment that causes heat)
>>Upon the temperature coming down, restart operation.
OK
Check Point 4 : Check Motor Capacitor
Check continuity of motor capacitor
>>If it is shorted, replace the capacitor.
OK
Check Point 5 : Replace Controller PCB
If Check Point 1- 4 do not improve the symptom, replace Controller PCB.
Indicate or Display:
Outdoor Unit : No indication
ERROR CODE : E : 12
Detective details:
When the condition that actual frequency of Indoor Fan is
below 1/3 of target frequency is continued more than 56 seconds.
5. Control PCB failure