2.4 TECHNICAL SPECIFICATIONS
Level accuracy
Trip delay
Reset delay
Minimum voltage threshold
Timing accuracy
Snapshot Events
2
2.4.1.23 OVERFREQUENCY (81O)
Pickup level
Dropout level
Level accuracy
Trip delay
Reset delay
Minimum voltage threshold
Timing accuracy
Snapshot Events
2.4.1.24 DIRECTIONAL POWER (32)
Current, Voltage
Number of stages
Pickup level (two stages)
Characteristic Angle (two stages)
Accuracy for primary magnitudes
Trip delay (two stages)
Timing accuracy
Block Time after close
Snapshot Events
Operate time:
2-16
±0.01 Hz of the reading
0.00 to 900.00 s. in steps of 0.01 s
0.00 to 900.00 s. in steps of 0.01 s
30 to 00V in steps of 1 V
±3.5% of operate time or 100 ms. (whichever is greater)
Selectable by setting
20.00 to 65.00 Hz in steps of 0.01 Hz
Pickup - 0.03 Hz
±0.01 Hz of the reading
0.00 to 900.00 s. in steps of 0.01 s
0.00 to 900.00 s. in steps of 0.01 s
30 to 00V in steps of 1 V
±3.5% of operate time or 100 ms. (whichever is greater)
Selectable by setting
Fundamental Phasor (primary values)
2
-10000.00 to 10000.00 MW (primary values) in steps of
0.01 MW
0.00 to 359.99 in steps of 0.01
±3% complete range
0.00 to 900.00 s in steps of 0.01 s
±3.5% of operate time or 50 ms. (whichever is greater)
0.00 to 900.00 s in steps of 0.01 s
Selectable by setting
< 45 ms at 50 Hz, typically
G650 Generator Protection & Control System
2 PRODUCT DESCRIPTION
GEK-113328A