Initial Settings
Backup
6
Select the item to set.
▲ ▼ →
7
set [Failure substitution]/
[Temperature support]/[Main
system setting].
▲ ▼ →
 Failure substitution
When this is set to ON, a system in
standby mode will perform the support
operation in case of alarm occurrence.
 Temperature support
In Cool mode: Performs the support
In Heat mode: Performs the support
 Main system setting
When "Set cycle" is set: System that
performs the preceding operation
When "Set cycle" is OFF: System that
always performs the operation
(The other system is a backup system.)
Note
 Depending on the model, the following display
appears and this function cannot be used.
 Setting cycle: The day when the setting is made is counted as one day.
 Temperature support: Immediately after the operation starts, the support
operation is not performed for up to 1 hour.
 Main system setting: Displays the system numbers that can be set.
48
(EN)
 Rotation setting (Continued)
operation when the room
temperature exceeds "set
temperature + set value".
operation when the room
temperature is below "set
temperature + set value".
ON
OFF
• 4 to 10 °C/
OFF
No.1
No.2