4
Out of specification
The positioner is operated outside speci-
fied operating conditions.
Note: If an event is assigned to the "No
message" status, this event does not have
any effect on the condensed state.
The condensed state is represented by the
following icons on the positioner display:
Condensed state
Maintenance alarm
Function check
Maintenance required/
Maintenance demanded
Out of specification
If the positioner has not been initialized, the
maintenance alarm icon (
the display as the positioner cannot follow
its reference variable.
If fault alarms exist, the possible source of
error is displayed in Code 49 onwards. In
this case, Err appears on the display.
The cause and recommended action are
listed in the code list (section 11).
66
EB 8387-3S EN
Positioner
display
Text e.g.
tESting, tunE or
tESt
blinking
) appears on
Example
Error caused by pin
position
Fault alarm output
The "Maintenance alarm" as the condensed
state causes the optional fault alarm output
to be switched.
4
The "Function check" condensed state
can also switch the fault alarm contact in
Code 32.
4
The "Maintenance required/demanded"
condensed state can also switch the fault
alarm contact in Code 33.

8.3.1 Confirming error messages

Enable configuration:
→ Code 3, display: No
Turn
Press
, Code 3 blinks.
→ YES
Turn
Press
, display:
Confirming error message:
→ Select error code which you
Turn
want to confirm.
Press
.
The error message is confirmed.