Precautions On Installation; Outdoor Unit Installation Diagram - Daikin RX30NMVJU Installation Manual

Hide thumbs Also See for RX30NMVJU:
Table of Contents

Advertisement

Precautions on Installation

• Check the strength and level of the installation surface so that the unit does not
cause any operating vibrations or noise after installation.
• Fix the unit in place securely using foundation bolts, as in the figure. (Prepare 4
sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all
separately available.)
• It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm)
from the foundation surface.

Outdoor Unit Installation Diagram

Max. allowable piping length
Min. allowable piping length
**
Max. allowable piping height
Additional refrigerant required for refrigerant
*
pipe exceeding 32.8ft (10m) in length.
Gas pipe
Liquid pipe
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
** The suggested shortest pipe length is 10ft (3m), in order to avoid
noise from the outdoor unit and vibration.
(Mechanical noise and vibration may occur depending on how
the unit is installed and the environment in which it is used.)
In sites with poor drainage,
use block bases for the
outdoor unit.
Adjust foot height until the unit
is level. Otherwise, water
leakage or pooling of water
may occur.
English
98-1/2ft (30m)
10ft (3m)
65-5/8ft (20m)
0.32oz/ft (30g/m)
O.D. 5/8 inch
(15.9mm)
O.D. 1/4 inch (6.4mm)
Allow 11-13/16" (300mm)
of work space below the
ceiling surface.
Wrap the insulation pipe with
finishing tape from bottom to
top.
Keep the piping length between
10ft (3m) and 98-1/2ft (30m).
Allow space for piping
and electrical servicing.
How to remove the stop
valve cover
1) Remove the screw on the
2) Slide the stop valve cover
How to attach the stop
valve cover
1) Insert the upper part of
2) Tighten the screw.
Where there is a danger of the unit
falling, use foot bolts, or wires.
CAUTION
Stop valve cover
stop valve cover.
downward to remove it.
the stop valve cover into
the outdoor unit.
4