Air to Air Heat Exchanger
2

Accessory parts

Name
Quantity
Shape
Installation manual
1
CD-ROM (Owner's manual
1
and Installation manual)
Owner's manual
1
Adapter
4
Screw
16/24
3

Cautions for installation

Make the inspection opening at the specific place on the ceiling so the constant cleaning or the equipment checking
of filter and heat exchange element can be performed.
• The inspection opening shown below is necessary to clean the heat exchange element and the filter as
required. If not cleaned, they are likely to get clogged, resulting in degradation of performance.
• Use forklift to carry in the Air to Air Heat Exchanger units and use winch or hoist at installation of them.
▼ VN-M150 to 1000HE
EA
(Exhaust
air)
Outdoor side
OA
(Outdoor
air)
150 to
250
Inspection Opening 450 × 450
For the inspection of Filters,
or more
Heat Exchange Elements,
Fans, Motors and Damper.
Model No.
A (mm)
VN-M150HE, M250HE
900
VN-M350HE
900
VN-M500HE, M650HE
1140
VN-M800HE, M1000HE
1189
7-EN
Installation Manual
Usage
(Hand it to the customers.)
(For other languages that do not appear in this manual, please refer
to the enclosed CD-ROM.)
(Hand it to the customers.)
Connection parts for the duct
Screws for attaching the adapter
B
C
RA (Return air)
Indoor side
Centre of gravity
SA (Supply air)
Heat exchange
B (mm)
C (mm)
Weight (kg)
900
290
36
900
290
38
1140
350
53
1189
400
70
Air to Air Heat Exchanger
▼ VN-M1500 and 2000HE
150 to
250
For the inspection of Filters,
Heat Exchange Elements,
Fans, Motors and Damper.
Unit: mm
element
2
2
2
2
– 4 –
1189
EA
RA (Return air)
(Exhaust
air)
Outdoor side
Indoor side
OA
SA (Supply air)
(Outdoor
air)
Centre of gravity
Inspection Opening 450 × 450
or more
Installation Manual
Unit: mm
810
Weight: 143 kg
Heat exchange element:
4
EN
8-EN