Installation Servicing Space - Daikin RXYSQ-TAV Installation Manual

Table of Contents

Advertisement

NOTE
If drain holes of the outdoor unit are covered by a
mounting base or by floor surface, raise the unit in
order to provide a free space of more than 100 mm
under the outdoor unit.
6.
I
NSTALLATION SERVICING SPACE
I
The connection piping outlet direction in the installation shown in
figure 4
is frontward or downward. The unit of numeric values is
mm.
I
When routing the piping backward, secure space of ≥250 mm on
the right side of the unit.
(A) In case of non-stacked installation
Suction side obstacle
Discharge side obstacle
Left side obstacle
Right side obstacle
Top side obstacle

Obstacle is present
(B) In case of stacked installation
1.
In case obstacles exist in front of the outlet side.
2.
In case obstacles exist in front of the air inlet.
I
NOTE
Do not stack more than one unit.
I
About 100 mm is required as the dimension
for laying the upper outdoor unit's drain pipe.
I
Get the portion A sealed so that air from the
outlet does not bypass.
Installation manual
6
(See figure 4)
1
In these cases, close the
bottom of the installation
frame to prevent the
discharged air from
being bypassed
2
In these cases, only
2 units can be installed.
3
In these cases, no
restriction of height L1.
This situation is not
allowed
A
≥1000
A
≥300
(C) In case of multiple-row installation (for roof top use, etc.)
1.
In case of installing one unit per row.
≥1000
2.
In case of installing multiple units (2 units or more) in lateral
connection per row.
H
Relation of dimensions between H, A and L is shown in the table
below.
0<L≤1/2H
L≤H
1/2H<L≤H
H<L
Installation impossible
≥100
≥2000
≥200
L
A
≥3000
≥600
≥1500
L
A
250
300
RXYSQ6TAV1B
VRV IV-S System air conditioner
4P482260-1 – 2017.03