Download Print this page

Cooper Lighting LTC2 Series Specification Sheet

Cooper lighting emergency lighting specification sheet

Advertisement

Quick Links

D I M E N S I O N S
2.4
1.5
9.4
O R D E R I N G I N F O R M AT I O N
S A M P L E N U M B E R : L T C 2
LTC2
Family
Voltage
LTC2=Load Transfer
Blank=120/277VAC
Circuit
COOPER LIGHTING - SURE-LITES
9.4
2.0
2.4
D E S C R I P T I O N
In the event of AC power
loss, the Sure-Lites
LTC2, Load Transfer
Circuit, automatically
switches normal light
fixtures to approved
emergency lights. The
LTC2, in conjunction
with an auxiliary
emergency power
generator or inverter,
will provide emergency
power to lighting
fixtures regardless of the
room switch position.
The LTC2 will operate up
to a maximum10A load.
The LTC2 is UL924 listed
for field retrofit
installation.
®
LTC2 SERIES
L o a d Tr a n s f e r C i r c u i t
E M E R G E N C Y L I G H T I N G
• 120/277VAC, 60Hz available
• Operates incandescent,
fluorescent, HID and other
loads; 10 Amps Max
• Matte black painted steel
housing
• Sized to fit inside ballast
channel
• Can be installed inside or
on top of fixture
• May be used with switched
fixtures
• Compatible with many
different lamp types
• Compatible with many
ballast types including
standard, rapid-start,
slimline, instant-start,
energy-saving, dimming
and electronic AC ballasts -
consult Cooper Lighting
Representative regarding
specific applications
• UL 924 Listed (dry
locations), UL Listed for
Retrofit/ Field Installation,
Life Safety NFPA 101,
NEC/OSHA
COOPER LIGHTING
669

Advertisement

loading