Mitsubishi Electric CITY MULTI PVFY-P18 NAMU-E Installation Manual page 11

Hide thumbs Also See for CITY MULTI PVFY-P18 NAMU-E:
Table of Contents

Advertisement

Available languages

Available languages

D
A
B
C
Step.12
A. Remove the Control box cover.
B. Unplug the LEV (CN60) and Thermistor (CN44) from the control
board and route the harness from control box area out through the
rubber grommet.
C. Remove the brackets which secure the coil assembly if not
already done.
D. Slide the coil assembly out of the air handler cabinet.
Step.13 Remove the Plate Guide Rear (3 screws) and Side Drain
Pan (4 screws) along with supporting brackets (4 screws) from the
coil assembly.
DETAIL B
PLATE GUIDE REAR
Step.14a Install the (2) drain pan seals included in the accessory
bag as shown above. These seals will cover the unused holes in the
SIDE
side drain pan to prevent leaks.
DRAIN
PAN
PLATE
GUIDE
REAR
Step.14b Reinstall the brackets to the opposite side of the Side
Drain Pan. The Side Drain Pan will be reinstalled on the opposite
side of the Coil Assembly. Reattach the Plate Guide Rear on the
opposite side of the coil assembly.
DETAIL B
DETAIL B
PIPING
SIDE
DRAIN
PAN