Heat Anticipator Setting (Electro-Mechanical Thermostats Only)14; Transformer Protection; Pre-Start-Up - Carrier K Series Installation Instructions Manual

15.2+ seer2 2-stage packaged air conditioner and gas furnace system with r-410a refrigerant single and three phase 2-5 nominal tons sizes 24-60
Table of Contents

Advertisement

PGR5 Series K: Installation Instructions
HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)
3-PHASE SHOWN
1-PHASE USES
TWO POWER
LEADS
EQUIP GR
CONTROL BOX
LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)
SPLICE BOX
Fig. 10 – High- and Control-Voltage Connections
IMPORTANT: Dehumidification control must open control circuit on
humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of either a 24
VAC dehumidistat or a thermostat which includes control of a 24 VAC
dehumidistat connection. In either case, the dehumidification control
must open the control circuit on humidity rise above the
dehumidification set point.
Heat Anticipator Setting (Electro-Mechanical
Thermostats only)
The room thermostat heat anticipator must be properly adjusted to
ensure proper heating performance. Set the heat anticipator, using an
ammeter between the W1 and R terminals to determine the exact
required setting.
NOTE:
For thermostat selection purposes, use 0.18 amp for the
approximate required setting. Failure to make a proper heat anticipator
adjustment will result in improper operation, discomfort to the occupants
of the conditioned space, and inefficient energy utilization; however, the
required setting may be changed slightly to provide a greater degree of
comfort for a particular installation.

Transformer Protection

The transformer is of the energy-limiting type, however a direct short
will likely blow a secondary fuse. If an overload or short is present,
correct overload condition and check for blown fuse on Indoor Fan
board or Integrated Gas Controller. Replace fuse as required with correct
size and rating.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
POWER
SUPPLY
FIELD-SUPPLIED
FUSED DISCONNECT
WHT(W1)
W/W1
YEL (Y)
Y1/Y
GRN(G)
G
RED(R)
THERMOSTAT
R
(TYPICAL)
BRN(C)
C
BLU(DH)
(DH ON 208/230 VAC
DH
MODELS ONLY)
PINK(Y2)
Y2
BLK(W2)
(W2 ON 208/230 VAC
W2
MODELS ONLY)
ENVIRONMENTAL, FIRE, EXPLOSION, ELECTRICAL
SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
1.
Follow recognized safety practices and wear protective goggles
when checking or servicing refrigerant system.
2.
Do not operate compressor or provide any electric power to unit
unless compressor plug is in place and secured.
3.
Do not remove compressor plug until all electrical sources are
disconnected and tagged.
4.
Relieve and recover all refrigerant from system before touching
or disturbing compressor plug if refrigerant leak is suspected
around compressor terminals.
5.
Never attempt to repair soldered connection while refrigerant
system is under pressure.
6.
Do not use torch to remove any component. System contains oil
and refrigerant under pressure.
A13016
To remove a component, wear protective goggles and proceed
as follows:
a.Shut off electrical power to unit and install lockout tag.
b.Relieve and reclaim all refrigerant from system using both
high- and low-pressure ports.
c.Cut component connecting tubing with tubing cutter and
remove component from unit.
d.Carefully unsweat remaining tubing stubs when necessary. Oil
can ignite when exposed to torch flame.
Use the Start-Up Checklist supplied at the end of this book and proceed
as follows to inspect and prepare the unit for initial start-up:
1. Remove access panels (see
2. Read and follow instructions on all DANGER, WARNING,
CAUTION, and INFORMATION labels attached to, or shipped
with unit.
3. Make the following inspections:
a. Inspect for shipping and handling damage, such as broken lines,
loose parts, disconnected wires, etc.
b. Inspect all field- and factory-wiring connections. Be sure that
connections are completed and tight.
c. Ensure wires do not touch refrigerant tubing or sharp sheet metal
edges.
d. Inspect coil fins. If damaged during shipping and handling,
carefully straighten fins with a fin comb.
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death or
property damage.
Do not purge gas supply into the combustion chamber. Do not use a
match or other open flame to check for gas leaks.
Use a commercially available soap solution made specifically for the
detection of leaks to check all connections. A fire or explosion may
result causing property damage, personal injury or loss of life.
14

Pre-Start-up

WARNING
!
Fig.
24).
WARNING
!

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pgr5 seriesHeil pgr536060kgp1g

Table of Contents