TROUBLESHOOTING

9-1. TROUBLESHOOTING
<Check code display by self-diagnosis and actions to be taken for service (summary)>
Present and past check codes are logged, and they can be displayed on the wired remote controller or controller board of out-
door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa-
rized in the table below. Check the contents below before investigating details.
Unit conditions at service
The trouble is reoccurring.
The trouble is not reoccurring.
OCH528B
Check code
Judge what is wrong and take a corrective action according
Displayed
to "9-3. SELF-DIAGNOSIS ACTION TABLE".
Conduct troubleshooting and ascertain the cause of the
Not displayed
trouble according to "9-4. TROUBLESHOOTING
OF PROBLEMS".
1 Consider the temporary defects such as the work of
protection devices in the refrigerant circuit including
compressor, poor connection of wiring, noise, etc.
Re-check the symptom, and check the installation
environment, refrigerant amount, weather when the
trouble occurred, matters related to wiring, etc.
Logged
2 Reset check code logs and restart the unit after finishing
service.
3 There is no abnormality in electrical component,
controller board, remote controller, etc.
1 Re-check the abnormal symptom.
2 Conduct troubleshooting and ascertain the cause of
the trouble according to "9-4. TROUBLESHOOTING
OF PROBLEMS".
Not logged
3 Continue to operate unit for the time being if the cause
is not ascertained.
4 There is no abnormality concerning of parts such as
electrical component, controller board, remote controller, etc.