SERVICE PARTS INFORMATION 3
Capillary tube & strainer
Check Point 1 : Check Capillary tube
Capillary tube normally has temperature difference between inlet and outlet as shown in
but if there is a big difference as shown in
In this case, replace Capillary tube.
Pipe (In)
Check Point 2 : Check Strainer
Strainer normally does not have temperature difference between inlet and outlet as shown in
but if there is a difference as shown in
Pipe (In)
, there is a possibility of inside clogged.
Pipe (Out)
Pipe (In)
, there is a possibility of inside clogged. In this case, replace Strainer.
Pipe (Out)
02-27
Pipe (In)
,
Pipe (Out)
,
Pipe (Out)