Service Parts; Fastener Torque Values - Carrier 38AUQA/B07 Installation And Service Instructions Manual

Heat pump condensing units
Table of Contents

Advertisement

5. Mix Totaline environmentally sound coil cleaner in a
1
2
/
gallon garden sprayer according to the instruc-
2
tions included with the cleaner. The optimum solution
temperature is 100F (38C).
NOTE: Do NOT USE water in excess of 130F (54C),
as the enzymatic activity will be destroyed.
6. Thoroughly apply Totaline
coil cleaner solution to all coil surfaces including the
finned area, tube sheets and coil headers.
7. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up-and-down motion.
Avoid spraying in horizontal pattern to minimize po-
tential for fin damage.
8. Ensure cleaner thoroughly penetrates deep into finned
areas.
9. Interior and exterior finned areas must be thoroughly
cleaned.
10. Finned surfaces should remain wet with cleaning so-
lution for 10 minutes.
11. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10-minute satu-
ration is achieved.
12. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray noz-
zle.
13. Replace top cover and rear corner posts.
environmentally sound

Service Parts

Listings of service parts for all units are available from the
Replacement Components Division's Electronic Parts
Information Catalog (EPIC). EPIC is available at Totaline
stores, distributor and service office parts departments and
on-line at HVACPartners.com.
When entering EPIC, the full unit model number is
required. The model number includes the Design Revision
reference value (see Fig. 2, Position 13). The unit model
number is available from the unit's information data plate.
(Do not use the "catalog number" when using EPIC. The
"catalog number" suppresses the Design Revision value;
failure to include Design Revision value may cause an
incorrect unit parts list to be displayed.) When using
EPIC, enter first four digits of the model number only.
Find appropriate model from sales packages listed. Be
sure to choose correct voltage and Design Revision.
EPIC is a product of RCD. To comment to the EPIC
program, use the "Comment" button inside the EPIC
program.

FASTENER TORQUE VALUES

Table 13 – Torque Values
Compressor mounting bolts
Condenser fan motor mounting bolts
Condenser fan hub setscrew
High-flow service port
Schrader-type service check valve
Compressor oil sightglass thread
Compressor to Compressor rail torque
Compressor rail to base pan torque
44
65--- 75 in–lbs
(734–847 N–cm)
20 2 in–lbs
(226 23 N–cm)
84 2 in–lbs
(949 136 N–cm)
96 10 in–lbs
(1085 23 N–cm)
2–3 in–lbs
(23–34 N–cm)
330 31 in–lbs
(23–34 N–cm)
120–168 in–lbs
(1356–1898 N–cm)
70 5 in–lbs
(791 57 N–cm)

Advertisement

Table of Contents
loading

This manual is also suitable for:

38auq38auqd/e0738auqa/b1238auqd/e12

Table of Contents