How to Connect Remote Controller
for Wire Operation
For indoor unit
1 Securely remove two screws at the front panel.
Type A: open the air inlet grille upward.
Type B: open two screw caps.
2. Slightly open the lower part of the front panel then pull the upper part of
the front panel toward you to remove it as shown on figure 1 .
3. Arrange the control wire as detail and specification as shown on figure 2.
4. Securely connect the control wire to terminal of Display unit as shown on
figure 3 (tighten firmly but not over 0.12 N·m (0.01 kgf·m)).
5. Set the control wire out from indoor unit same portion as power supply
and connecting cable as shown on figure 3 . (Notch for wire out)
6. Reassembly the indoor unit by reverse process of 1 to 2.
Type A
1
Screw
Type B
1
Screw
* Wire size 28-22AWG
or 0.08-0.32 mm
2
Outer diameter not over 4.7 mm,
control wire length 30 m. or less.
Notch for wire out
3
Control wire
Indoor unit
Control wire
Remote controller
Front panel
Screw
Front panel
Screw
Screw cap
70 mm
2
5 mm
Control wire
Terminal
Display unit
For remote controller
1. Remove cover of remote controller by sliding down and take it out.
2. If batteries are exist, please take them out. The combination of using
wire controller and batteries may cause of batteries explosion.
3. Make hole for insert control wire by use screwdriver break the plastic for
cover hole as shown on figure 4.
4. Insert control wire from rear side of remote controller as shown on figure 5.
5. Fix control wire which arrange as shown on figure 6 and 7 to terminal
by provided screws (tighten firmly but not over 0.25 N·m (0.03 kgf·m)).
6. Set control wire through gutter way at rear side of remote controller as
shown on figure 8.
7. Fix provided screw (Ø3.1×16L) on the wall to hang remote controller as
shown on figure 9.
8. Mark and arrange hole for fix below screw (Ø3.1×25L) as shown on
figure 9.
9. Assembly battery cover which provided with accessory bag then use
provide screw (Ø3.1×25L) to fix battery cover together with wall as
shown on figure 0 (tighten firmly but not over 0.15 N·m (0.02 kgf·m)).
10. Reassembly cover of remote controller.
4
Plastic for cover hole
7
Type A
Control wire
* Terminals for wiring can be either on right (type A) or left (type B), depending on the controller
packed in carton.
Control wire
Hole for hang
remote controller
Remote controller
8
Type A
Battery cover
Tighten firmly but not over
0.15 N·m (0.02 kgf·m)
*Remark : 1. Recommend to use double insulation lead wire for connect
remote control and air conditioner.
2. For wire operation, 1 remote control can control only 1 indoor unit.
3. In wire operation, remote controller will return to initial
condition (PRESET, TIMER and CLOCK will return to initial
condition) when user shutdown power supply of air conditioner.
8
5
6
30 mm
10 mm
* Wire size 28-22AWG
Control wire
or 0.08-0.32 mm
Outer diameter not over 4.7 mm,
control wire length 30 m. or less.
Type B
Terminal
Screw (Ø3.1×16L)
for hang remote
controller
Wall
Remote controller
Screw (Ø3.1×25L)
for fix battery cover
Type B
Screw
2
Control wire
9
0