6.2.
Additional Refrigerant Charging
Refrigerant charge is only in the outdoor unit prior to shipment.
NOTICE:
Outdoor unit has been pre-charged with refrigerant. The refrigerant charge is not included in the
indoor unit and the refrigerant pipe.
The amount of the additional refrigerant charge is dependent on the diameter and length of the
liquid refrigerant pipe which is determined by the actual field installation requirement.
Record the additional refrigerant charge for future maintenance.
Calculation of the Additional Refrigerant Charge
(Σ Length of Liquid Pipeφ9.52×54+Σ Length of Liquid Pipeφ6.35×22)-880
The maximum additional refrigerant charge value is 800g.
If the calculated value exceeds 800g, the additional refrigerant charge should be 800g
If the calculated value is less than 800g, the additional refrigerant charge is the calculated
value.