6.2.
Additional Refrigerant Charging
•
Refrigerant charge is only in the outdoor unit prior to shipment.
NOTICE:
•
Outdoor unit has been pre-charged with refrigerant. The refrigerant charge is not included in the
indoor unit and the refrigerant pipe.
•
The amount of the additional refrigerant charge is dependent on the diameter and length of the
liquid refrigerant pipe which is determined by the actual field installation requirement.
•
Record the additional refrigerant charge for future maintenance.
•
Calculation of the Additional Refrigerant Charge
•
(Σ Length of Liquid Pipeφ9.52×54+Σ Length of Liquid Pipeφ6.35×22)-880
•
The maximum additional refrigerant charge value is 800g.
•
If the calculated value exceeds 800g, the additional refrigerant charge should be 800g
•
If the calculated value is less than 800g, the additional refrigerant charge is the calculated
value.