1. Precaution installation stand. 1.1 Safety Precaution It may cause injury, accident, or damage to the To prevent injury to the user or other people product. and property damage, the following instructions Be sure the installation area does not must be followed. deteriorate with age.
Page 5
It may cause corrosion on the product. Corrosion, arrives. particularly on the condenser and evaporator fins, There is risk of property damage, failure of product, could cause product malfunction or inefficient or electric shock. operation. Do not open the inlet grill of the product during operation.
Page 6
The chemical in batteries could cause burns or other your skin or clothes, wash it well with clean water. health hazards Do not use the remote of the batteries have leaked.
2. Function Indoor unit Operation by remote controller Sensing by room temperature Room temperature sensor. Pipe temperature sensor. Room temperature control Maintain the room temperature in accordance with the setting temperature. Anti-freezing control in cooling Prevent the water being frozen on evaporator by sensing the evaporator pipe temperature in cooling mode Time Delay Safety control Restarting is for approx.
Page 8
Outdoor unit Power relay control The unit has 3 mins delay between continuously ON/OFF operations. Low noise air flow system Bird tail propeller fan makes the outdoor unit run more quietly. Hydrophilic aluminum fin The hydrophilic fin can improve the heating efficiency at operation mode. 4 way valve control It is only operated in the heating operation mode except defrosting operation.
7. Installation details 7.1 Wrench torque sheet for installation Outside diameter Torque inch Kgf.m Ф6.35 Ф9.52 Ф12.7 7.2 Connecting the cables The power cord of connect should be selected according to the following specifications sheet. Grade Unit 7.3 Pipe length and the elevation Standard Max.
Page 17
compressor, reduce the cooling capacity, and could lead to a malfunction of unit. Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the refrigeration cycle. Procedure 1.
7.5 Pumping down (Re-installation) Procedure 1. Confirm that both the 2-way and 3-way valves are set to the opened position. Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2.
7.6 Re-air purging (Re-installation) Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the closed position. 2. Connect the charge set and a charging cylinder to the service port of the 3-way valve. Leave the valve on the charging cylinder closed. 3.
7.7 Balance refrigerant of the 2-way, 3-way valves Procedure: 1. Confirm that both the 2-way and 3-way valves are set to the open position. 2. Connect the charge set to the 3-way valve’s service port. Leave the valve on the charge set closed. Connect the charge hose with the push pin to the service port.
7.8 Evacuation Procedure: 1. Connect the vacuum pump to the charge set’s centre hose. 2. Evacuation for approximately one hour. Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less]. 3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7.9 Gas charging Procedure: 1. Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. 2. Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
9. Electronic function 9.1 Abbreviation T1: Indoor ambient temperature T2: Pipe temperature of indoor heat exchanger T3: Pipe temperature of outdoor heat exchanger T4: Outdoor ambient temperature 9.2 Display function 9.2.1 Icon explanation on indoor display board. Auto indicator This indicator illuminates when the air conditioner is in AUTO operation. PRE.-DEF.
It will take 3 minutes every time when compressor starts. It will take only 1 minute when the unit is powered on at first time. 9.3.4 Temperature sensor protection at open circuit or short circuit. 9.3.5 Protection of indoor fan speed. When indoor fan speed is too low (lower than 300rpm for 50 seconds), the unit will stop and LED display error code and can’t return to normal operation automatically.
Page 27
-0.5 -1.0 When the machine is running and ΔT(=room temp. – setting temp.) changes, the frequency of compressor will rise or descend a grade (7 minutes after starting). After starting, if ΔT stays in a zone for 3 minutes, the frequency will change as follow: Zone A : Current frequency rise a grade till the maximum grade F8.
Auto fan in cooling mode acts as follow: high medium 9.5.7 Condenser high temperature protection function(in cooling and drying mode) If T3 60 for 5 seconds, compressor will stop immediately, and the machine will not resume until T3 52 . 9.6 Drying mode 9.6.1 Indoor fan speed is fixed at breeze grade and can’t be changed.
Page 29
9.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is preferential. Auto fan action in heating mode. medium high 9.7.3 After start the operation frequency of compressor submits to following rule: Remark: ΔTcon can be changed among 0, -2,- 4 , the default is 0 When the machine runs, if ΔTh stays in a zone for 3 minutes, action of frequency is as follow: Zone A: Elevate the current frequency one grade, and not stop until the maximum grade.
Page 30
When the units are running, if the following two items are satisfied the units start defrosting: a) The units runs with T3 3 for 40 minutes and T3 keeps lower than -6 for more than 3 minutes. b) The units runs with T3 3 for 80 minutes and T3 keeps lower than -4 for more than 3 minutes.
or setting temperature. 9.7.9 Turbo function in heating mode. (press the “TURBO” button on remote controller) Elevate current frequency (excluding F8) to a higher grade. If indoor fan is in low speed or pause caused by defrosting or anti-cold-wind function, frequency of compressor will not be elevated one grade until these limit has been released.
high high Outdoor fan action in heating mode Outdoor fan action in cooling & drying mode (including heating in auto mode). (including cooling in auto & forced mode). 9.11.3 Outdoor fan action in cooling & drying mode(including cooling in auto & forced mode). Please refer to the pic.
10. Troubleshooting Safety Because of there are capacitors in PCB and relative circuit in outdoor unit, even shut down the power supply, electricity power still are kept in capacitors, do not forget to discharge the electricity power in capacitor. Electrolytic Capacitors (HIGH VOLTAGE! CAUTION!) Bulb (25-40W)
10.1 Indoor Unit Error Display Display LED STATUS EEPROM parameter error Indoor / outdoor units communication protection Zero-crossing signal error Indoor fan speed out of control Open or short circuit of outdoor ambient or condenser temperature sensor Open or short circuit of indoor room or evaporator temperature sensor Inverter module (IGBT) over-strong current protection Over voltage or too low voltage protection Temperature protection of compressor top.
10.2 Diagnosis and Solution 10.2.1 E0 (EEPROM parameter error) error diagnosis and solution Circuit or software error on indoor PCB Replace indoor PCB 10.2.2 E1 (indoor / outdoor units communication protection) error diagnosis and solution Disconnect the power supply, after 1 minute, connect the power supply , turn on the unit with remote controller Does the unit work normally?
Page 36
10.2.4 E3 (indoor fan speed out of control) diagnosis and solution Is the indoor fan motor Repair the connector and connector and connection reconnect good? Is voltage being applied to the fan motor? Indoor PCB is defective. (rang 90v-160v between Replace the indoor PCB.
Page 37
10.2.8 P1 (over voltage or too low voltage protection) diagnosis and solution. Be sure the power supply is Is the power supply good? normal when using the units Replace the outdoor e-box. 10.2.9 P2 (temperature protection of compressor top) diagnosis and solution. Is the connection Does compressor Reconnect and retest.
Black - Red 418Ω ±8% (20 ) Blue - Red 10.3.3 Indoor Fan Motor 277Ω±8% (20 ) (Model:RPG13H for S3025, RPG20E for S3032). Measure the resistance value of each winding by using the multi-meter. Yellow - Blue 277Ω±8% (20 )
Page 39
378Ω±8% (20 ) for RPG20E 10.3.4 Step Motor (Model: MP2835 for S3025, MP24GA for S3032). Measure the resistance value of each winding by using the multi-meter. Position Resistance Value Blue - Red Pink - Orange 200Ω±7% (25 ) Pink - Yellow Yellow - Red 10.3.5 Temperature Sensors.