Summary of Contents for Aprilaire Zoned Comfort Control 6302
Page 1
Model 6303 & 6302 Zoned Comfort Control ® Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS 61001212 B2206667E 2.19 English 1...
SPECIFICATIONS INPUT RATINGS FIGURE 1 – ZONE PANEL DIMENSIONS IN INCHES (mm) Voltage: 18-30VAC 50/60 Hz MAXIMUM CURRENT Damper output per zone (fused): 18VA at 158°F, 30VA at 90°F Zone panel and thermostats (fused): 18VA at 158°F, 30VA at 90°F Zone panel consumption: 4VA max Note: Use 18 or 20 AWG solid (non-stranded) wire 9.66 (245)
INSTALLATION MOUNTING 1. Separate the zone panel cover from the FIGURE 3 FIGURE 4 – MOUNTING HOLE LOCATIONS base. See FIGURE 3. 2. Use the base as a USE TWO SCREWS WHEN template to drill ATTACHING TO A WALL STUD mounting holes.
WIRING WARNING FIGURE 6 – WIRE TIE MOUNTS 120 volts may cause serious injury from electrical shock. Sudden operation may cause serious injury from moving parts. Leave power disconnected until installation is complete. Follow these steps for all system connections. Wiring will vary depending on equipment.
SELECT AND WIRE THE TRANSFORMER TO THE CONTROL PANEL 1. Note: The HVAC equipment transformer cannot be used for power. A separate transformer should be used to FIGURE 7 – TRANSFORMER power the zone panel, thermostats and dampers. 2. Wire 24VAC from transformer to the POWER, R and C terminals (see FIGURE 7).
ZONE DAMPER WIRING • Run 2-conductor thermostat wire for spring return dampers (normally open or normally FIGURE 8 – NORMALLY OPEN / POWER CLOSE DAMPERS closed). • Run 3-conductor thermostat wire for power open/power close dampers. • Multiple dampers for the same zone can be wired in parallel as shown in FIGURES 8 &...
DISCHARGE AIR TEMPERATURE SENSOR (INCLUDED) • Wire the discharge air temperature sensor Model 8052 to the “DAT” terminals as FIGURE 10 – DISCHARGE AIR TEMPERATURE SENSOR shown. See FIGURE 10. • Maximum distance of the sensor from the zone panel is 300 feet. •...
SEQUENCE OF OPERATION The 6303/6302 zone panel is for single stage heat pump applications, with a single stage of auxiliary heat. The zone panel is a heat call priority system with automatic heating/cooling changeover after 20 minutes of operation. If two opposing (heating/cooling) thermostat calls exist while the system is idle, the heating call will be satisfied first.
WARRANTY REGISTRATION Visit us online at www.aprilaire.com to register your Aprilaire product. If you do not have online access, please mail a postcard with your name, address, phone number, email address, product purchased, model number, date of purchase, and dealer name and address to: Research Products Corporation, P.O. Box 1467, Madison, WI 53701.