Siemens 7PG2114 Application Manual page 36

Hide thumbs Also See for 7PG2114:
Table of Contents

Advertisement

X
θ
=
1
Tan
R
θ
=
87
o
θ
=
=
cos
00544
R
Z
S
S
R
= 0.07765 ohms/km (Primary)
L
R
= 10 x 0.07765 = 0.7765Ω (Primary)
L
X
= 0.28978 ohms/km
L
X
= 10 x 0.28978 = j2.8978Ω (Primary)
L
Total impedance for a through fault at the remote busbar =
Z
+ Z
= (R
+ R
) + (X
+ X
S
L
S
L
S
(0.0544 + 0.7765) + j(1.0876 +2.8978)
Z
= 0.8309 + j3.9854 ohms
F
=
2
+
2
Z
R
X
=
+
2
. 0
8309
. 3
9854
Z
Z
= 4.071 ohms
F
Through Fault Current =
3
19.05x10
=
=
I
4.68kA
F
4.071
Through fault current = 4.68kA compared to 17.5kA Busbar fault current due to the effect of the line impedance.
19.05kV
©2010 Siemens Protection Devices Limited
Ω
=
X
Z
&
S
S
)
L
2
Zs
17.5kA
7PG2113/4/5/6 Solkor Applications Guide
θ
=
Ω
sin
. 1
0876
(Primary)
Z
L
4.68kA
Chapter 7 Page 36 of 49