Ex-DI 4xNAMUR
The intrinsic safety of the interconnection of I/O module, sensors and cabling must be
proven by calculating the safety-related characteristic values. These values are stated
in the respective Ex certificates or on the data sheet of the cable.
Table 1-1
Pin assignment of Ex-DI 4xNAMUR
Termin
Assign
al
ment
1
DI
+
0
3
UV
0
5
DI
+
2
7
UV
2
Equipping
Check the I/O module for damage! You may only plug undamaged I/O modules
onto the BaseUnit.
The coding element on the BaseUnit latches into place the first time that a I/O
module is plugged in. This prevents the insertion of a wrong module. This
mechanical coding may not be changed.
When configuring the ET 200SP HA and the ET 200SP, you must observe the
permissible number of I/O modules (see the respective operating instructions).
WARNING
Permissible number of I/O modules
When configuring the ET 200SP HA and the ET 200SP, you must observe the rules
specified below for the maximum configuration and load of the Ex power modules.
Load on the Ex power modules
Ensure that the current consumption of the Ex I/O modules of an Ex module group
does not exceed the permissible output current of the Ex power module.
The maximum current requirement of the I/O module can be found in the technical
specifications.
Permissible output current of the Ex power module > ∑ I
the respective potential group
Commissioning
You must observe the national regulations during commissioning.
12
Termin
Assign
al
ment
2
DI
+
1
4
UV
1
6
DI
+
3
8
UV
3
Explanations
Terminals 1;2;5;6:
DI
+: Input signal, channel n
n
Terminals 3;4;7;8:
UV
: Encoder supply, channel n
n
of all I/O modules of
max
Ex-DI 4xNAMUR
A5E50377423-AB, 03/2023