7. Mechanical coding of the plug-in module

Where there is a danger of inserting a module in the
wrong slot, the possibility has to be excluded as
prescribed in EN 50 020, Section 6.3.2. To this end,
the units must be supplied already equipped with
coding inserts as shown in Figure 3 and 4.
Order Type
808-617
Back
A
B
C
D
E
F
G
H
I
K
L
M
Power supply
24...60 V DC/AC
Fig. 3. Coding of the plug-in module SIRAX TV 808 in standard
(non-Ex) version.
Order Type
808-615
Back
A
B
C
D
E
F
G
H
I
K
L
M
Power supply
24...60 V DC/AC
Fig. 4. Coding of the plug-in module SIRAX TV 808 in
[EEx ia] IIC version, output intrinsically safe.
Legend to Fig. 3 and 4:
= With set of code,
16
808-618
Back
A
B
C
D
E
F
G
H
I
K
L
M
Power supply
85...230 V DC/AC
808-616
Back
A
B
C
D
E
F
G
H
I
K
L
M
Power supply
85...110 V DC /
85...230 V AC
= Without set of code

8. Electrical connections

The isolating amplifier SIRAX TV 808 is plugged onto a
backplane BP 902. A 96 pin connector (model C, DIN 41 612)
establishes the electrical connections between the isolating
amplifier and the backplane. The pin connections can be
seen from Fig. 5.
Please refer to our backplane instructions for the back-
plane wiring.
Make sure that the cables are not live when
making the connections!
The 230 V power supply is potentially
dangerous!
In the case of "Intrinsically safe" explosion-
proof versions [EEx ia] IIC, the supplementary
information given on the type examination
certification, the EN 60 079-14, and also
local regulations applicable to electrical
installation in explosion hazard areas must
be taken into account.
Note that, ...
... the data required to carry out the prescribed
measurement must correspond to those
marked on the nameplate of SIRAX TV 808
(
measuring input,
power supply!)
... the total loop resistance connected to the output
(receiver plus leads) does not exceed the
maximum permissible value R
"Measuring output" in Section "6. Technical
data" for the maximum values of R
... the measurement input and output cables
should be twisted pairs and run as far as
possible away from heavy current cables!
In all other respects, observe all local regulations
when selecting the type of electrical cable and
installing them!
measuring output,
max., see
ext.
!
ext.