August 24, 2006
1. PRODUCT NAME
EARLY SUPPRESSION FAST RESPONSE PENDENT SPRINKLER VK510
Sprinkler Base Part No. 12080 (1" NPT) or Part No. 12200 (25 mm BSP)
Available since 2003.
†The Sprinkler Identification Number (SIN) is stamped on the sprinkler deflector.
2. MANUFACTURER
THE VIKING CORPORATION
210 N. Industrial Park Road
Hastings, Michigan 49058, U.S.A.
Telephone:
(269) 945-9501
Technical Services: (877) 384-5464
Fax:
(269) 945-9599
e-mail:
techsvcs@vikingcorp.com
3. PRODUCT DESCRIPTION
Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler SIN VK510 is an extension of prior ESFR technology.
The addition of a larger K-Factor allows ESFR performance at lower end-head pressures than ESFR K14 sprinklers. K25.2
ESFR sprinklers can:
Eliminate the use of in-rack sprinklers when protecting high-piled storage of certain specified materials up to 40 ft. (12,2
m) with ceilings up to 45 ft. (13,7 m)*
Reduce or eliminate the need for a system fire pump.
Provide flexibility when sizing system piping.
Provide a maximum ceiling-to-element distance of 18 inches (457 mm). (Refer to Design Criteria on page 124 d.)
Viking SIN VK510 ESFR Pendent Sprinklers may be used in the protection of ordinary types of storage. However, they are
primarily intended to protect the following types of storage, which tend to produce severe-challenge fires: palletized and solid
pile storage and single, double, multiple row, and portable open rack storage (no open-top containers or solid shelves).
Viking ESFR Pendent SIN VK510 Sprinklers provide protection of most common storage materials, including:
Encapsulated or unencapsulated Class I, II, III, and IV commodities*.
cULus Listed for protection of cartoned unexpanded plastic commodities and FM Approved for protection of cartoned and
uncartoned unexpanded plastic commodities*.
FM Approved for protection of exposed expanded polystyrene and exposed expanded polyurethane commodities*.
In addition, some storage arrangements of rolled paper, flammable liquids, aerosols, and rubber tires may be protected by
Viking ESFR Pendent Sprinkler SIN VK510.
4. TECHNICAL DATA
LISTINGS AND APPROVALS
cULus Listed: Category VNWH (Listed as a Specific Application ESFR Sprinkler)
FM Approved: Class 2026
Viking ESFR Pendent SIN VK510 Sprinkler is cULus Listed, FM Approved and VdS Approved.
*
Refer the Approval Chart on page 124 c and Design Criteria on pages 124 d-e for cULus and FM approval requirements that must be
followed.
CHARACTERISTICS
Rated to 175 psi (12 bar) water working pressure.
Factory tested hydrostatically to 500 psi (34,5 bar)
Note: Units of measure in parentheses may be approximations.
Form No. F_100102
TECHNICAL DATA
ESFR PENDENT SPRINKLER
SIN VK510 (K25.2)
(K25.2)
Replaces page 124 a-d, dated June 2, 2006
(Reformatted, added new wrench 13635W/B.)
Sprinkler 124 a

Advertisement

loading

Summary of Contents for Viking SIN VK510

  • Page 1 Provide a maximum ceiling-to-element distance of 18 inches (457 mm). (Refer to Design Criteria on page 124 d.) Viking SIN VK510 ESFR Pendent Sprinklers may be used in the protection of ordinary types of storage. However, they are primarily intended to protect the following types of storage, which tend to produce severe-challenge fires: palletized and solid pile storage and single, double, multiple row, and portable open rack storage (no open-top containers or solid shelves).
  • Page 2: Ordering Instructions

    Temperature Suffix (°F/°C): 165°/74° = C, 205°/96° = E For example, Sprinkler VK510 with 1” NPT threads, Brass finish, and 165 °F/74 °C temperature rating = Part No. 12080AC. ACCESSORIES (Also refer to the “Sprinkler Accessories” section of the Viking data book.) Sprinkler Wrenches: •...
  • Page 3 August 24, 2006 Sprinkler 124 c ESFR PENDENT SPRINKLER TECHNICAL DATA SIN VK510 (K25.2) Approval Chart ESFR Pendent Sprinkler SIN VK510 Maximum 175 PSI (12 bar) WWP Nominal Listings and Approvals Overall Length Base Part K-Factor (Refer also to Design Criteria on pgs 124 d-e.)
  • Page 4: Design Criteria

    IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Viking ESFR Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data, the latest applicable Factory Mutual Loss Prevention Data Sheets, including 2-2 and 8-9, the latest standards of VdS, NFPA, and any other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and standards whenever applicable.
  • Page 5 Firefighter Eliminator F type 50% propylene glycol/water mixture, with a freeze temperature rating (freeze point) of -26 °F (-32.2 °C). Refer to data page 45 a-j “Viking ESFR Cold Storage System” in the Freezer Storage section of the Viking data book.
  • Page 6: Installation

    Installation standards require sprinklers to be tested and, if necessary, replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., NFPA 25) and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required.
  • Page 7 ESFR PENDENT SPRINKLER TECHNICAL DATA SIN VK510 (K25.2) C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers installed.
  • Page 8 THIS PAGE INTENTIONALLY LEFT BLANK Replaces page 124 a-d, dated June 2, 2006 Form No. F_100102 (Reformatted, added new wrench 13635W/B.)