Toshiba MCY-MUG0401HSW-E Installation Manual page 17

Outdoor unit
Hide thumbs Also See for MCY-MUG0401HSW-E:
Table of Contents

Advertisement

[Installation positions of Leak Detector]
Indoor Unit
>
h
2.2
=
0
Leak Detector
<
=
<
=
* It must be placed within a horizontal distance of 10 meters and on the wall in the room where the indoor unit
is installed.
However, when it does not enter the field of view on a straight line from Leak Detector, it is within 7 m at the
shortest horizontal distance without obstacles and installed on the wall in the room where the indoor unit
is installed.
NOTE
Leak Detector generates visual and auditory warnings.
31-EN
Indoor Unit
>
h
1.8
=
0
10 m*
<
300 mm
300 mm
=
[The examples for safety device installations]
The location of Leak Detector varies depending on the safety system and the room.
Incorrect
d
d
a
1
b
b
c
c
e
d
e
d
a
2
b
c
c
d
e
a
3
b
c
c
e
d
e
d
a
4
b
b
c
c
a : Outdoor unit, b : Indoor unit, c : Leak Detector, d : Shut-off Valve unit, e : Battery kit
– 16 –
Correct
• Install Leak Detector
in same room as the
connected indoor
unit.
d
d
a
b
b
c
c
• Group setting of
indoor unit across
Shut-off Valve unit is
not possible
b
• Only one Leak
Detector can be
d
connected to indoor
units with a group
e
setting.
a
b
b
b
c
• Multiple Leak
Detectors cannot be
connected to one
indoor unit.
e
d
e
d
a
b
b b
b
c
c
Case
EN
32-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mcy-mug0501hsw-eMcy-mug0601hsw-e