Checking code
Meaning, detecting method
5301
IAC sensor/
1 If IAC
circuit
before the inverter starts, or
abnormality
If IAC
ing inverter operation after 5
seconds has passed since the
inverter started when the INV
board's SW1-1 is OFF.
[Inverter error detail : 6]
2 If the current sensor (ACCT)
miss-wiring is detected during
inverter operation.
[Inverter error detail : 13]
7130
Different
An exclusive R22 refrigerant indoor
indoor model
unit was connected to a R407C
connected
refrigerant heat source unit.
abnormality
3 Arms is detected just
6) The circuit board is defective.
3 Arms is detected dur-
1) An error was made in the MAIN
board of the heat source unit (re-
placed with the wrong circuit
board).
2) An error was made in selecting the
indoor unit (installation error).
3) An error was made in the indoor
unit's circuit board (replaced with
the wrong circuit board).
Cause
–117–
Checking method & Countermeasure
If none of the items in 1) to 5) is appli-
cable, and if the trouble reappears
even after the power is switched on
again, replace the circuit board by fol-
lowing procedure (when replacing the
circuit board, be sure to connect all
the connectors, ground wires, etc.
securety)
1 If the problem is solved after the
G/A board only is replaced, then the
G/A board is defective.
2 If the problem is not solved, rein-
stall the INV board and replace the
INV board. If the problem is solved,
the INV board is defective.
3 If the problem is not solved by 1
and 2 above, replace both boards.
If the model name plate on the heat
source unit says that it is an exclusive
R22 model, and if error "7130" has oc-
curred, the MAIN board for the heat
source unit is a R407C model circuit
board, so replace it with the MAIN
board for the R22 model.
If the model name plate for the indoor
unit is an exclusive R22 model, install
a unit which can also operate with
R407C.
If the model name plate on the indoor
unit indicates that it is also capable of
operating with R407C, and error "7130"
occurs, the indoor unit's circuit board
is for an exclusive R22 model, so re-
place it with the circuit board for a unit
which is also capable of using R407C.