Siemens WZU-485E-MOD Operating Instructions Manual

Siemens WZU-485E-MOD Operating Instructions Manual

Modbus module

Advertisement

Available languages

Available languages

Quick Links

en
Operating instructions
1.
Safety Information
Comply with ESD protection measures.
Avoid short-circuits on the PCB.
When connecting, turn off the mains supply.
Route connecting cables only through the bush
sleeves of the meter.
Do not cut the bush sleeves shorter than necessary
because this may lower the degree of protection.
2.
Description of function
WZU-485E-MOD is an add-on communication module for the
following types of meters: T550
higher) and T550
(UC50...)
.
The module is intended and preconfigured for data transmis-
sion using the Modbus RTU protocol on RS485.
Micro USB
connector
Interface to meter
Note: An external power pack must power the module
(not included in the module's scope of delivery).
3.
Items delivered
1.
Communication module WZU-485E-MOD
2.
Screw connector for RS485 interface and power supply
3.
Jumper bridge (red)
4.
Installation and assembly
Up to 2 communication modules can be installed.
WZU-485E-MOD
Modbus module WZU-485E-MOD
(UH50...)
(firmware 5.15 and
Supply and data
connection terminal
1
2
3
4
1
Note: WZU-485E-MOD may only be combined with
an M-Bus module in slot "module 2". Only one of them
may be operated in fast read-out mode with an up-
date interval shorter than 15 min.
Installing the communication module
The communication modules are connected via a 6-pole reac-
tion-free connector so that installation or replacement is possi-
ble at any time.
To install a communication module proceed as follows:
Press the 4 side lugs of the housing cover inwards and
remove the cover.
Put the communication module into the correct position.
Note: The module WZU-485E-MOD may only be
fitted at slot "module 1".
Place the communication module carefully in both guide
slots and push it in.
Wait for the module indication on the meter display (Loop 4:
"Modul1 MI / G4").
To connect the power supply and the communication cable
of WZU-485E-MOD, open 2 sleeves matching the cross
section of the respective cables.
Note: Open the cable sleeves in such a way that they
enclose the cable tightly.
Guide cables through the bush sleeves from the outside.
Connect the the power supply to terminals 24V and GND,
and the communication cable to terminals A+ and B-.
Note: For the connection to the screw terminal, a slot
screwdriver with 2.5 mm tip is needed.
Attention: Connecting the power supply to terminals
A and B can cause permanent damage to the module.
Insert the screw connector into its counterpart on the com-
munication module.
Secure the cables with the metal strain relief.
Note: The jumper bridge must not be inserted during
operation.
5.
LCD display
Note: Both display range and data displayed can differ
from this description depending on the meter parame-
terization. Certain button functions can also be blocked.
Subject to change without prior notice
26.01.2017
Service button (under
the housing cover)
Slot „module 1"
Slot „module 2"
Bushing for power
cable
Bush sleeves
5
Original
1

Advertisement

loading

Summary of Contents for Siemens WZU-485E-MOD

  • Page 1 Do not cut the bush sleeves shorter than necessary cable because this may lower the degree of protection. Description of function Bush sleeves WZU-485E-MOD is an add-on communication module for the Note: WZU-485E-MOD may only be combined with following types of meters: T550 (UH50…) (firmware 5.15 and an M-Bus module in slot “module 2”.
  • Page 2 Proceed as follows to leave the parameterization operation:  Press button 1 until is displayed.  Press button 2. Note: The primary M-Bus address can also be set with the Service Software UltraAssist. WZU-485E-MOD Subject to change without prior notice...
  • Page 3: Technical Data

    AC 16...28 V Direct current permissible range DC 10...32 V Consumption <50mA (typically <20 mA / 24 V) Recommended fuse fuse T 100 mA Galvanic Isolation From the meter From the RS485 network WZU-485E-MOD Subject to change without prior notice...
  • Page 4 After a data request with the broadcast address “0“, the module reads new data from the meter, but sends no message.  The module does not return exception responses to invalid data requests. WZU-485E-MOD Subject to change without prior notice...
  • Page 5 *XX (binary) needs to be converted to decimal. Example 0x00C5 10^(1) kWh 10^(3) l Format / = 10 kWh 1=kWh = 1 m³ Unit = 0,01 MWh Table 3: Header (data address 13) WZU-485E-MOD Subject to change without prior notice...
  • Page 6: Einbau Und Montage

    Das Modul ist für die Datenübertragung nach dem Modbus- Durchführungstüllen RTU Protokoll über RS485 geeignet und vorkonfiguriert. Hinweis: Das WZU-485E-MOD darf nur mit einem M- Bus Modul auf Steckplatz „Modul 2“ kombiniert wer- den. Nur eines der beiden Module darf im Schnellaus- lesemodus mit einem Aktualisierungsintervall kleiner 15 Min.
  • Page 7: Lcd-Anzeige

    Die nächste Stelle rechts blinkt. Wiederholen Sie obige Schritte für alle Stellen.  Geben Sie eine Adresse zwischen 1 und 247 ein. Das LCD zeigt kurzzeitig ein Stern-Symbol zur Bestätigung an. Bei Fehleingaben können Sie erneut parametrieren. Änderungen vorbehalten WZU-485E-MOD...
  • Page 8: Technische Daten

    Externen Widerstand (120 Ohm) benutzen Spannungsversorgung Wechselspannung Zulässiger Bereich: AC 16...28 V Gleichspannung Zulässiger Bereich: DC 10...32 V Leistungsaufnahme <50mA (typisch <20 mA bei 24 V) Empfohleme Absicherung 100 mA träge Galvanische Trennung Vom Zähler Vom RS485 Netzwerk Nein Änderungen vorbehalten WZU-485E-MOD...
  • Page 9 Das Modul aktualisiert die gespeicherten Zählerdaten binnen 5 Sekunden nach einer Datenanfrage.  Nach einer Datenanfrage mit der Rundrufadresse „0”, aktualisiert das Modul die gespeicherten Zählerdaten, sendet aber keine Antwort.  Das Modul gibt keine Fehlermeldung (exception response) bei ungültigen Datenanfragen zurück. Änderungen vorbehalten WZU-485E-MOD...
  • Page 10 0=MJ 10^(XX) l 10^(XX) kWh 1=kWh XX (binär) muss in dezimal umgewandelt werden. Beispiel 0x00C5 10^(1) kWh Format / 10^(3) l = 10 kWh 1=kWh = 1 m³ Einheit = 0,01 MWh Tabelle 3: Header (Datenadresse 13) Änderungen vorbehalten WZU-485E-MOD...