Pentair CODELINE 40E30N User Manual
Pentair CODELINE 40E30N User Manual

Pentair CODELINE 40E30N User Manual

4 inch end entry membrane housing for ro applications

Advertisement

Quick Links

CODELINE
- 40E30N
®
4 iNCH eNd eNTrY MeMBrANe HOusiNg FOr rO APPLiCATiONS
user guide
ARTICLE CODE: 526003
advanced filtration
user guide

Advertisement

Table of Contents
loading

Summary of Contents for Pentair CODELINE 40E30N

  • Page 1 CODELINE - 40E30N ® 4 iNCH eNd eNTrY MeMBrANe HOusiNg FOr rO APPLiCATiONS user guide ARTICLE CODE: 526003 advanced filtration user guide...
  • Page 2: Table Of Contents

    Content Page No. Danger High Pressure Device Important Safety Precautions General Information Installation Opening the vessel 4 - 5 Opening the vessel: Contamination Removal Opening the vessel: Removing the Head Opening the vessel: Removing Head Assembly Replacing Elements 6 - 7 Replacing Elements: Removing Elements Replacing Elements: Inserting Elements Replacing Elements: Closing the vessel...
  • Page 3: Danger High Pressure Device

    DANGER – HIGH PRESSURE DEVICE This vessel may cause loss of life, severe bodily harm, or property damage if not correctly installed, operated and maintained. Read and understand all guidelines given in this bulleting before attempting to open, operate or service this vessel.
  • Page 4: Installation

    Installation Regardless of when or by whom your vessel may have been installed, there are a few quick checks you should make before use. Check that each vessel is:  Mounted with compliant material (Polyurethane saddle) between the fiberglass shell and any rigid frame. ...
  • Page 5: Opening The Vessel

    Opening the vessel CAUTION: DO NOT tap on fittings as this WARNING: Relieve pressure from vessel could damage the ports. before beginning this procedure. best accomplished by using Codeline Removal Tool, part number 50303, which Contamination removal is available from your supplier. This can also be accomplished using a screwdriver and a Metal oxidation products and mineral deposits pair of pliers if the tool is not readily...
  • Page 6: Opening The Vessel: Removing Head Assembly

    your finger behind the ring as it continues to exit the groove. Removing the head assembly 6. Repeat same procedure for opposite end of Removal of retaining ring the vessel. 7. As soon possible after removal, 3. Once the retaining ring has been removed, disassemble and check all head components, examine the area for burrs or dings which as described in Rebuilding the Head and...
  • Page 7: Replacing Elements

    Replacing elements The following procedures are provided for information only. Elements should be installed in accordance with the element manufacturer’s recommendations. Where conflicts exist, contact the element manufacturer or Codeline for clarification. To replace elements, proceed as follows. Removing Elements Installation of the End Plug Assembly into the vessel 1.
  • Page 8: Replacing Elements: Closing The Vessel

    10. Push each element downstream into the shell as it is installed until the element is Closing the vessel fully engaged with the downstream head. If the elements are hard to push, make sure the brine seal is properly installed and you 6.
  • Page 9: Head Disassembly

    Head disassembly NOTE: Head Rebuilding should be performed in a clean work area. Dust or dirt on O-rings or other parts can scratch inner surfaces, with subsequent leakage. 2. Using a small screwdriver or similar tool 1. Using a small screwdriver or similar tool remove the adapter Seal from the groove in remove the Plug Seal.
  • Page 10: Head Assembly

    Head assembly 4. Insert the Head Seal O-ring into the groove 1. Use only head components in as-new on the outside diameter of the End Plug. condition. Use new O-rings each time the head is assembled. 2. Cover O-rings with an even layer of Parker Super O-Lube silicon lubricant or the lubricant recommended by your element...
  • Page 11: Refurbishing Parts Inspecting Parts

    Codeline® PENTAIR WATER INDIA PVT. LTD. L / 52 – 55, VERNA INDUSTRIAL ESTATE, VERNA, GOA, INDIA – 403 722 WWW.CODELINE.COM Note: The information and data contained in this document are based on our general experience and are believed to be correct. They are given in good faith and are intended to provide a guideline for the selection and use of our products.

This manual is also suitable for:

526003

Table of Contents