Intermatic AG65033 Installation Instructions
Intermatic AG65033 Installation Instructions

Intermatic AG65033 Installation Instructions

Type 1 or type 2 surge protection device (spd)

Advertisement

Quick Links

IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
Risk of Fire or Electric Shock
WARNING
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Intended for indoor or outdoor use.
• Installation and/or wiring must be in accordance with national and local electrical code and/or Canadian Electrical Code requirements.
• Installation and service to be performed by a qualified licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 50,000 rms symmetrical amperes.
• This unit contains no serviceable parts.
AVERTISSEMENT
• L'installation et/ou le câblage doivent être conformes aux exigences du code de l'électricité local en vigueur et/ou du Code canadien de l'électricité.
• L'installation et l'entretien doivent être effectués par un technicien ou électricien qualifié.
• Convient à un circuit capable de fournir PAS plus de 50 000 A efficaces symétriques.
• Cet appareil ne contient aucune pièce réparable.
NOTICE
NOTICE
• Thoroughly read instructions before installing SPD Unit.
• This product does not protect against lightning strikes.
Type 1 installation:
A typical installation of a type 1 SPD will be connected between the secondary of the service transformer and the line side of
the service panel. This installation is intended to be installed without overcurrent protection to the SPD.
Type 2 installation:
A typical installation of a type 2 SPD will be connected to the load side of the service panel and is intended to be installed with
overcurrent protection to the SPD.
1. Determining location:
• Ensure conductor lengths are as short and straight as possible for best performance. Do not coil excess wire. The SPD
functions best if all bends in wires are rounded, ideally to a 4" radius. Hard 90 degree bend will reduce efficiency. Cut
all leads to the correct length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be mounted outside.
• Bracket part number AG1BRKT is also available if needed.
2. Connect wires as shown within diagrams. If your application does not match one of the diagrams below consult your
supplier.
3. Ensure all mounting and electrical connections are correct and securely fastened. Once energized the green indicator
LED will be ON.
Maintenance:
AC Voltage SPD:
• Periodically check SPD to ensure green indicator LED is ON. If green LED is OFF, protection has diminished and the
SPD should be replaced immediately.
Line
600 V
Line
600 V
600 V
Line
347 V
Neutral/Grounded
600 VAC Three wire plus Ground
Found at Service Entrances and
Meter Cabinets.
Model AG65033/AG6503C3/AG6503L3
Type 1 or Type 2 Surge Protection Device (SPD)
Risque d'incendie ou de choc électrique
347/600 VAC WYE 3 PHASE
BLACK
347 V
BLACK
347 V
BLACK
WHITE
INSTALLATION INSTRUCTIONS
Line
600 V
Line
600 V
600 V
Line
Neutral
Ground
347/600 VAC Four wire plus Ground
Found in Main Disconnect Switches,
Main Distribution panels, Load Centers
Sub panels and equipment locations.
BLACK
347 V
BLACK
347 V
BLACK
347 V
WHITE

Advertisement

loading

Summary of Contents for Intermatic AG65033

  • Page 1 INSTALLATION INSTRUCTIONS Model AG65033/AG6503C3/AG6503L3 Type 1 or Type 2 Surge Protection Device (SPD) IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS Risk of Fire or Electric Shock WARNING • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.