Electrical Connection
SQM5... actuators are equipped with two removable
conduit connection plates located on the upper corner
of the gear housing. Each plate is provided with two
threaded connections for 1/2-inch NPSM conduit
connectors. The use of flexible 14 gauge or smaller
stranded wire is recommended.
NOTE: SQM5... Actuators require a single-source,
single-phase power supply.
Figure 5. AGA56.41/42/43... Terminal and Trim Potentiometer Boards.
Siemens Industry, Inc.
Figure 4. Basic Functional Diagram of AGA56.4...
Grounding
To avoid electro-magnetic interference, SQM5...
actuators must be grounded. The ground screw is
located to the right of the AUTO/MAN switch (below
the shaft release button).
CAUTION:
Disconnect the circuit board wire marked 51
during high voltage testing. Reconnect it to
the grounding terminal after the test.
Document No. 129-400
Installation Instructions
October 2, 2009
Page 3 of 5