Design Criteria - Viking FREEDOM VK494 Technical Data Manual

Residential concealed pendent sprinkler

Advertisement

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Viking VK494, 4.9 K-factor Residential Concealed Pendent Sprinkler
For systems designed to NFPA 13D or NFPA 13R. For systems designed to NFPA 13, refer to the Design Criteria. For Ceiling types refer
Sprinkler Base
Part Number
1
23707
Max. Coverage Area
6
W X L
Ft. X Ft.
(m X m)
12 X 12
(3.7 X 3.7)
14 X 14
(4.3 X 4.3)
16 X 16
(4.9 X 4.9)
18 X 18
(5.5 X 5.5)
20 X 20
(6.1 X 6.1)
Part number shown is the base part number. For complete part number, refer to the current Viking price schedule.
1.
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
2.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional
3.
approvals. Refer also to Design Criteria.
Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and European Union.
4.
Meets New York City requirements, effective July 1, 2008.
5.
For areas of coverage smaller than shown, use the "Flow" and "Pressure" for the next larger area listed. Flows and pressures listed are per sprinkler. The distance from
6.
sprinklers to walls shall not exceed one-half the sprinkler spacing indicated for the minimum "Flow" and "Pressure" used.
Other paint colors are available on request with the same listings as the standard finish colors. Stainless Steel cover plates are not available with any finishes or paint.
7.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label inside the cover assembly.
Refer to Figure 3.
Accepted Cover Plate Finishes are: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or
8.
Painted Black
.
7
C-UL-US-EU Listed as corrosion resistant - Electroless Nickel PTFE (ENT)
9.
UL Listing Requirements (C-UL-US-EU)
When using Viking Residential Concealed Pendent Sprinkler VK494 for systems designed to NFPA 13D or NFPA 13R, apply the listed areas of cover-
age and minimum water supply requirements shown in the Approval Chart.
For systems designed to NFPA 13: The number of design sprinklers is to be the four contiguous most hydraulically demanding sprinklers. The minimum
required discharge from each of the four sprinklers is to be the greater of the following:
The flow rates given in the Approval Chart for NFPA 13D and NFPA 13R applications for each listed area of coverage, or
Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the "design area" in accordance with sections 9.5.2.1 or 10.2.4.1.2 of the current
edition of NFPA 13.
Minimum distance between residential sprinklers: 8 ft. (2.4 m).
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No. F_080415 - Best Practices for Residential Sprinkler Handling and Installation.
Also refer to Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinances, and standards, whenever
applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities
Having Jurisdiction.
Form No. F_012116
Rev 01
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Approval Chart
to current editions of NFPA 13, 13R or 13D
Thread Size
SIN
NPT
VK494
1/2"
Flow
Pressure
GPM (LPM)
PSI (bar)
155 °F (68 °C), 200 °F (93 °C)
Temperature Rated Sprinklers
13
(49.2)
13
(49.2)
13
(49.2)
17
(64.4)
20
(75.7)

DESIGN CRITERIA

(Also refer to the Approval Chart.)
:
September 7, 2022
BSPT
15 mm
Deflector
to Ceiling
7.0
(0.48)
7.0
(0.48)
7.0
Refer to
(0.48)
Figure 2
12.0
(0.83)
16.7
(1.15)
Footnotes
FREEDOM
®
CONCEALED PENDENT
SPRINKLER VK494 (K4.9)
Nominal K-factor
U.S.
metric
2
4.9
70.6
Listings and
Approvals
Installation
Type
cULusEU
Concealed with
Cover Plate As-
See Footnotes 8, & 9
sembly.
See Footnote 7.
Page 6 of 8
RESIDENTIAL
Maximum Water
Working Pressure
175 psi (12 bar)
Minimum
3,5
Spacing
Ft. (m)
4
8
(2.4)