Setup/
Addr
Dir
Runtime
Setup
3022
R/W
Setup
3023
R/W
Setup
3030
R/W
Setup
3031
R/W
Setup
4000
R/W
Setup
4004
R/W
Setup
4020
R/W
Setup
5000
R/W
Setup
5001
R/W
Setup
5040
R/W
TR50 - User Guide
Non-
Name
Volatile
NV
3
NV
cfgLCDDim-
Brightness
NV
cfgLCD DIM Time
NV
cfgLCD OFF time
NV
cfgTemperature-
Unit
NV
cfgTVOCUnit
NV
cfgLEDAndLC-
DEnable
NV
cfgModbusAuto-
BaudrateEnable
V
cfgModbusFr-
ameCntClear
NV
cfgLocalDetec-
tionEnable
Bits
SKU
Type/Unit
Num
3D/5D
enum/
16
int16
3D/5D
int16
16
3D/5D
int16
16
3D/5D
int16
16
3N/
bit/bool-
1
3D/
ean
5N/5D
5N/5D
bit/bool-
1
ean
3D/5D
bit/bool-
1
ean
3N/
bool
1
3D/
5N/5D
3N/
bool
1
3D/
5N/5D
3N/
bool
1
3D/
5N/5D
Range
1: Auto (default)
2: Manual + AQI( as the
static page)
3. Manual + Temperature
(as the static page)
4: Manual + Humidity (as
the static page)
5: Manual + CO
(as the
2
static page)
6: Manual + PM2.5 (as the
static page)
7: Manual + TVOC (as the
static page)
8: Manual + no static page
10-40
3-10
0, 10-30
-Farenheit: 0
-Celsius: 1
-ppb: 0
-ug/m3: 1
ON or OFF
TRUE or FALSE
TRUE or FALSE
TRUE or FALSE
26
Default
1
40
10
0
Farenheit
ppb
ON/1
TRUE
TRUE
TRUE