Dyna-Glo GUH50NE/LE Operating Instructions And Owner's Manual page 17

Gas unit heater for residential/commercial use
Table of Contents

Advertisement

FUEL CONVERSION Section 3: RATE TAG CONVERSION INSTRUCTIONS
Step 13
Connect main electrical power, and turn main gas
supply back on. Turn up thermostat to call for heat.
When the main burners light using soapy water check all
connections thoroughly for gas leaks. Allow the heater
to operate for at least 5 minutes, then observe the main
burner flame. A hard blue flame extending into the tube is
normal. Slight yellow tipping is acceptable. There is no air
adjustment to the burner.
Step 14
Remove the data tag for their respective gases. Remove
label and place over the existing portion of the tag. This
tag is preprinted with all the correct information for the
converted heater.
Step 15
Remove the converted information tag from the kit and fill
in the information. Then place this tag below the updated
rating tag on the unit.
Step 16
Replace any panels and operate heater following all
warnings/cautions and instructions in the operator's
manual and labels.
TABLE 4
NATURAL GAS MANIFOLD PRESSURES - IN. W.C. (KPA)
GUH50 / GUH80
0-2000 (0-610)
GUH50 / GUH80
3.5" WC (0.872 KPA)*
*NO ADJUSTMENT REQUIRED
TABLE 5
LP/PROPANE GAS MANIFOLD PRESSURES - IN. W.C. (KPA)
GUH50 / GUH80
0-2000 (0-610)
GUH50 / GUH80
10"WC (2.62 KPA)*
*NO ADJUSTMENT REQUIRED
TABLE 6
INLET PRESSURES
Natural Gas
Propane
ALTITUDE FT. (M)
2000-4500 (610-1370)
2.8" WC (0.697 KPA)
ALTITUDE FT. (M)
2000-4500 (610-1370)
8.5"WC (2.12 KPA)
MAX - 14" WC (3.49 kPa)
MIN - 5" WC (1.25 kPa)
MAX - 14" WC (3.49 kPa)
MIN - 11" WC (2.74 kPa)
GAS UNIT HEATER
17